Viking VGRT7486G Installationsanweisungen

Seite von 8
9
8
• This rangetop may be installed directly
adjacent to existing 36” (91.4 cm) high
base cabinets.
IMPORTANT: The top of the side trim
MUST be 3/8” (.95 cm) above the
adjacent base cabinet countertop.
• The rangetop CANNOT be installed
directly adjacent to sidewalls, tall cabinets,
tall appliances, or other side vertical
surfaces above 36” (91.4 cm) high. There
must be a minimum of 12” (30.5 cm) side
clearance from the rangetop to such
combustible surfaces above the 36” 
(91.4 cm) counter height.
• Within the 12” (30.5 cm) side clearance 
to combustible vertical surfaces above 
36” (91.4 cm), the maximum wall cabinet
depth must be 13” (33.0 cm) and wall
cabinets within this 12” (30.5 cm) side
clearance must be 18” (45.7 cm) above
the 36” (91.4 cm) high countertop.
• Wall cabinets above the rangetop must be
a minimum of 58” (147.3 cm) above the
rangetop cooking surface for the full width
of the rangetop. This minimum height
requirement does not apply if a rangetop
hood is installed over the cooking surface.
BURN HAZARD
To avoid risk of personal injury;
the use of cabinets for storage
above the appliance may result
in a potential burn hazard. Combustible
items may ignite, metallic items may
become hot and cause burns. If a cabinet
storage is to be provided the risk can be
reduced by installing a rangehood that
projects horizontally a minimum 5” (12.7 cm)
beyond the bottom of cabinets.
Note: Based on 24” (61 cm) deep cabinet.
Note: Minimum clearance for back wall is 
3/4” (1.9 cm) with backguard or high-shelf.
Note: If a rangetop hood is installed, wall
cabinets above the rangetop have a
different minimum clearance height.
The bottom of a standard hood should
be 30” (76.2 cm) min. to 36” (91.4 cm)
max. above the countertop. This would
typically result in the bottom of the hood
being 66” (167.6 cm) to 72” (182.9 cm)
above the floor. Refer to the hood
installation instructions for additional
information. These dimensions provide
for safe and efficient operation of the
hood.
Wall Installation
Island Installation
Note: 6” (15.2 cm) min. with island trim and
combustible rear wall. 0” with island trim
and non-combustible rear wall.
Note: Minimum clearance for
back wall is 3/4” (1.9 cm) with
backguard or high-shelf.
Important: This rangetop comes standard
with an Island Trim. There must be a
minimum of 6” (15.2 cm) clearance from
rear of rangetop to a combustible wall.
Clearances from non-combustible
materials are not part of the ANSI Z21.1
scope and are not certified by CSA.
Clearances to non-combustible materials
must be approved by the authority having
jurisdiction.
Clearance Dimensions 
(Proximity to Cabinets)
Clearance Dimensions
(Wood/Composite Overlay)