Panasonic Valve Regulated Lead Acid Batteries 12V7.2A LC-R12V72P Benutzerhandbuch

Produktcode
LC-R12V72P
Seite von 9
 VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to
modification without notice. Contact Panasonic for the latest information.
Testing conditions
Discharge: 0.25 CA, End voltage: 1.7V/2V
Charging: 2.275V/2V, Constant-voltage control,
               current: 0.15 CA
Conventional products
Trickle long life series
10          20           30          40          50          60           70
Temperature <˚C>
Ser
vice lif
e (y
ears)
15
10
5
3
1
0.5
0.1
(Test condition)
Discharge : 0.25 CA
Cut-off voltage : 1.75V/cell
Capacity check by every 3 months
Charge : 2.30V/cell
Constant-voltage control
Maximum current : 0.4 CA
Temperature : 20˚C to 23˚C
Time (years)
Capacity (%)
120
100
80
60
40
20
0                              1                            2                            3                             4
(Test condition)
Discharge : 0.25 CA
Cut-off voltage: 1.7V/2V
Charge : 2.275V/2V
Constant-voltage control 0.2 CA
Discharge frequency : once every 21 days
Trickle long 
life series
Conventional
products
 0           2           4           6            8          10         12          14         16
50˚C discharge period (months)
Conversion to 25˚C period (years)
Dur
ation of discharge (min
utes)
300
250
200
150
100
50
0
0            1            2             3            4               5            6            7
Conversion to 20˚C period (cycles)
0                1                  2                   3                  4                   5
b) Trickle (Float) life
Trickle life of the battery is largely dependent on the
temperature condition of the equipment in which the
battery is used, and also related to the type of the
battery, charge voltage and discharge current. The
respective Figures show the influence of temperature
on trickle life of the battery, an example of trickle
(float) life characteristics of the battery, and the test
result of the battery life in an emergency lamp.
Influence of Temperature on Trickle life
Trickle life characteristics at 122°F (50°C)
Trickle (Float) life characteristics (LC-R)
CHARACTERISTICS - CONTINUED