Perlick HP24FS35 Installationsanweisungen

Seite von 13
PERLICK RESIDENTIAL INSTALLATION MANUAL
6
perlick.com
PREPARING THE SPACE
If the unit is to be installed under 
a countertop, it is recommended 
that the countertop be supported by a structure other 
than the unit itself to prevent damage to the unit. 
Make sure the floor under the 
unit is level with the surrounding 
finished floor. Protect a finished floor with plywood, 
cardboard, or some other suitable material before 
moving the unit into place. Failure to do this may 
result in damage to the floor.
1). Make sure the space opening is correctly sized for 
the unit. See chart below for finished rough opening 
requirements:  
CAUTION
CAUTION
HP15 15” Signature Series
Height
Depth
Width
34-3/8” minimum,
35-1/2” maximum
24”
15”
HP24 24” Signature Series
Height
Depth
Width
34-3/8” minimum,
35-1/2” maximum
24”
24”
HP48 48” Signature Series
Height
Depth
Width
34-3/8” minimum,
35-1/2” maximum
24”
48”
HC24 24” C-Series
Height
Depth
Width
34-3/8” minimum,
35-1/2” maximum
24”
24”
HA24 24” ADA-Compliant Series
Height
Depth
Width
32-1/2”
24”
24”
HH24 18” Shallow-Depth Series
Height
Depth
Width
32-1/2”
18”
24”
NOTE: For a cabinet door to open properly, the door must  
open a minimum of 90°. Use a minimum 3” filler in corner 
installations to assure a full 90° opening. Allow 25” clearance 
in front of unit for full door swing and shelf/drawer pull out for 
all units.
2). Check that the following are level and square:
•  Front and interior opening
•  Installation opening and floor surface
•  Countertop bottom front edge
NOTE: The floor under the unit must be at the same level as the 
surrounding finished floor.
To prevent possible damage to the 
countertop, do not place heavy 
objects on countertop directly over unit.
 
INSTALLING THE UNIT
1). Plug the unit into the 15 amp grounded electrical 
outlet located within the installation opening. With power 
applied to the unit, check that the lighting and cooling 
functions operate properly. Turn off the power to the wall 
outlet at the circuit breaker.
2). With all surfaces in the installation opening square and 
level, refer to Figure 4 on page 7 and perform the following 
steps to level the unit:
•  At the front of the opening, measure from the floor to 
the bottom of the front edge of the countertop.
•  Measure from the floor surface to the top of the unit at 
the rear corners.
•  Adjust the unit legs so these two measurements are 
equal. Using an adjustable wrench or pliers, turn legs 
clockwise to lower the unit or counterclockwise to raise it. 
NOTE: Legs should not extend more than 3/4” from the bottom 
of the unit. 
3). Slide the unit into position in the opening. Make sure 
the rear leveling legs slide under the ant-tip brackets. Push 
the unit into the opening until the bottom front edge of 
the unit is flush with the surrounding cabinetry, or until the 
rear legs are tight against the anti-tip brackets.
4). Shim the front of the unit so the front face is flush 
with the surrounding cabinetry. Adjust the front legs to 
support the countertop at the shimmed height. Using 
an adjustable wrench or pliers, turn the legs clockwise to 
lower the unit or counterclockwise to raise it. Countertop 
should be resting on top of the unit.
NOTE: Countertop should be resting evenly on entire top of the 
unit. Shim if necessary to prevent damage to the countertop.
CAUTION