Higher volumes of air exhausted by the vent
system result in better overall removal of smoke
and fumes from the kitchen. Longer duct runs
and greater numbers of duct transitions reduce
air volume, therefore
it is extremely important
to keep duct runs as short and straight as
possible.
To ensure that your installation meets this
requirement, add the actual straight length of
duct to the equivalent straight length of all duct
fittings to determine the total equivalent straight
length of duct. (Refer to the table above, which
shows various common duct fittings with their
equivalent straight lengths for various common
duct sizes). If this total equivalent straight
length is less than or equal to the maximum
limits specified, then the installation is proper.
Consider the duct size that corresponds to the
majority of the duct used in the installation.
3 1/4" x 10" 90° Elbow
3 1/4" x 10" 45° Elbow
3 1/4" x 10" Wall Cap
3 1/4" x 10"
90° Flat Elbow
Transistion
3 1/4" x 10" to Round
45° Elbow - Round Duct
90° Transistion
3 1/4" x 10" to 8" Round
90° Elbow - Round Duct
15 Feet
7 Feet
2 Feet
20 Feet
6" Diameter - 4 Feet
7" Diameter - 4 Feet
8" Diameter - 4 Feet
10" Diameter - 4 Feet
6" Diameter - 6 Feet
7" Diameter - 5 Feet
8" Diameter - 3 Feet
10" Diameter - 2 Feet
25 Feet
6" Diameter - 12 Feet
7" Diameter - 10 Feet
8" Diameter - 7 Feet
10" Diameter - 5 Feet
Model
#
Duct
Size
Maximum Equivalent Straight Lengths
REMP3
REMP16
ERV/
PRV
8”
50’
60’
10”
40’
70’
3 1/4”x10”
40’
60’
3. Add (1) and (2) to determine the
total equivalent straight length of the
complete duct system: 20’ + 15’ + 4’
= 39’ total equivalent straight duct
length.
4. For the remote system with 3 ¼” x
10” duct, the maximum allowable total
equivalent straight length of duct is 40
feet. Thus, this proposed installation is
proper.
After determining that your proposed ductwork
meets the maximum duct length requirement,
proceed with the location planning.
Finished floor
3 1/4" x 10"
90° Elbow
3 1/4" x 10"
90° Elbow
ERV36
Motor cover
Epicure 36"
Cooktop
ERV36
Wall board
Countertop
Anchoring leg
End of ESG
support shelf
REMP3/16
Supplied
Transition
ATD2 (p/n 13768)
Cabinet back
3 1/4" x 10"
Duct
Stud wall
Outside wall
3 1/4" x 10"
to round
transition
8” or 10” DIA.
Sample problem:
Given a remote system installation having 20
feet of 3 ¼” x 10” rectangular duct, one (1)
90-degree 3 ¼” x 10” elbow, and one (1) 3 ¼”
x 10” to 8” or 10” round transition, would this
installation be proper?
Solution:
1. Add the total length of straight duct:
20’ (of 3 ¼” x 10”) = 20’.
2. Using Table above, determine the
equivalent straight length of all duct
fittings: 90-degree 3 ¼” x 10” elbow
= 15’. 3 ¼” x 10” to 8” or 10” round
transition = 4’.
ERV Raised Floor Island Installation
4. Thermal breaks, such as a
short section of non-metallic
duct, should be used in areas
of extreme cold.
5. A back-draft damper at the duct
outlet may also be required.
6. Do not use flexible metal duct.
7. Do not use ductwork that is
smaller in cross-sectional area
than the recommended size
duct.
8. Do not rely on duct tape alone
to seal duct joints. Use sheet
metal screws as require to
support the duct weight.
9. The raised vent and
cooking appliance(s) must
be removable if service is
required.
10. Be certain that the ductwork
does not interfere with floor
joists or wall studs.
11. It is important to keep a
minimum number of turns in
the duct run, and to keep the
run as short as possible.
12. Do not restrict the air flow
by reducing the duct cross-
sectional areas when making
hard joints or squeezing
through a tight area.
13. with concrete slab
construction, "box-in" the
ductwork to prevent it from
collapsing when the wet
concrete is poured. Also allow
room for electrical conduit.
14. Cross-drafts or air currents
caused by adjacent open
windows or doors, hVAC
outlets, ceiling fans, and
recessed ceiling lights reduce
vent efficiency.