Higher volumes of air exhausted by the vent 
system result in better overall removal of smoke 
and fumes from the kitchen.  Longer duct runs 
and greater numbers of duct transitions reduce 
air volume, therefore 
it is extremely important 
to keep duct runs as short and straight as 
possible.
To ensure that your installation meets this 
requirement, add the actual straight length of 
duct to the equivalent straight length of all duct 
fittings to determine the total equivalent straight 
length of duct. (Refer to the table above, which 
shows various common duct fittings with their 
equivalent straight lengths for various common 
duct sizes).  If this total equivalent straight 
length is less than or equal to the maximum 
limits specified, then the installation is proper.  
Consider the duct size that corresponds to the 
majority of the duct used in the installation.
3 1/4" x 10" 90° Elbow
3 1/4" x 10" 45° Elbow
3 1/4" x 10" Wall Cap
3 1/4" x 10"
90° Flat Elbow
Transistion
3 1/4" x 10" to Round
45° Elbow - Round Duct
90° Transistion
3 1/4" x 10" to 8" Round
90° Elbow - Round Duct
15 Feet
7 Feet
2 Feet
20 Feet
6" Diameter - 4 Feet
7" Diameter - 4 Feet
8" Diameter - 4 Feet
10" Diameter - 4 Feet
6" Diameter - 6 Feet
7" Diameter - 5 Feet
8" Diameter - 3 Feet
10" Diameter - 2 Feet
25 Feet
6" Diameter - 12 Feet
7" Diameter - 10 Feet
8" Diameter - 7 Feet
10" Diameter - 5 Feet
Model
#
Duct
Size
Maximum Equivalent Straight Lengths
REMP3
REMP16
ERV/
PRV
8”
50’
60’
10”
40’
70’
3 1/4”x10”
40’
60’
3.   Add (1) and (2) to determine the 
total equivalent straight length of the 
complete duct system: 20’ + 15’ + 4’ 
= 39’ total equivalent straight duct 
length.
4.   For the remote system with 3 ¼” x 
10” duct, the maximum allowable total 
equivalent straight length of duct is 40 
feet. Thus, this proposed installation is 
proper.
After determining that your proposed ductwork 
meets the maximum duct length requirement, 
proceed with the location planning.
Finished floor
3 1/4" x 10"
90° Elbow
3 1/4" x 10"
90° Elbow
ERV36
Motor cover
Epicure 36"
Cooktop
ERV36
Wall board
Countertop
Anchoring leg
End of ESG
support shelf
REMP3/16
Supplied
Transition
ATD2 (p/n 13768)
Cabinet back
3 1/4" x 10"
Duct
Stud wall
Outside wall
3 1/4" x 10"
to round
transition
8” or 10” DIA.
Sample problem: 
Given a remote system installation having 20 
feet of 3 ¼” x 10” rectangular duct, one (1) 
90-degree 3 ¼” x 10” elbow, and one (1) 3 ¼” 
x 10” to 8” or 10” round transition, would this 
installation be proper?
Solution:
1.  Add the total length of straight duct: 
 
20’ (of 3 ¼” x 10”) = 20’.
2.   Using Table above, determine the 
equivalent straight length of all duct 
fittings: 90-degree 3 ¼” x 10” elbow 
= 15’. 3 ¼” x 10” to 8” or 10” round 
transition = 4’.
ERV Raised Floor Island Installation
4.  Thermal breaks, such as a 
short section of non-metallic 
duct, should be used in areas 
of extreme cold.  
5.  A back-draft damper at the duct 
outlet may also be required.
6.  Do not use flexible metal duct. 
7.  Do not use ductwork that is 
smaller in cross-sectional area 
than the recommended size 
duct.
8.  Do not rely on duct tape alone 
to seal duct joints. Use sheet 
metal screws as require to 
support the duct weight.
9.  The raised vent and 
cooking appliance(s) must 
be removable if service is 
required.
10.  Be certain that the ductwork 
does not interfere with floor 
joists or wall studs.
11.  It is important to keep a 
minimum number of turns in 
the duct run, and to keep the 
run as short as possible.
12.  Do not restrict the air flow 
by reducing the duct cross-
sectional areas when making 
hard joints or squeezing 
through a tight area.
13.  with concrete slab 
construction, "box-in" the 
ductwork to prevent it from 
collapsing when the wet 
concrete is poured. Also allow 
room for electrical conduit.
14.  Cross-drafts or air currents 
caused by adjacent open 
windows or doors, hVAC 
outlets, ceiling fans, and 
recessed ceiling lights reduce 
vent efficiency.