Planning the Installation
Any openings in the wall behind the appliance or in the 
floor underneath it must be sealed.
Both the gas supply piping and shut-off valve and the 
electrical outlet must be located so they do not interfere 
with the range when it is installed. 
All dimensions shown are based on standard American 
cabinets 36 inches (914mm) high at the finished 
countertop by 24 inches (610mm) deep, with a 25 
inch (635mm) overall countertop depth. All minimum 
clearances shown MUST be maintained.
If cabinet storage space is to be provided directly above 
the range, the risk of personal injury may be reduced by 
installing a ventilating hood that projects horizontally a 
minimum of 5 inches beyond the face of the cabinets.
The installation must allow for the following:
Access to the gas shut-off valve when the unit is 
installed.
Access to the electrical outlet, when the range is in 
place.
The gas supply piping, gas shut-off valve and the 
electrical junction box or receptacle must be located 
so they do not interfere with the range when it is 
installed.
The electrical outlet and gas shut off valve must 
be located so that the range can be pulled out for 
service while the appliance remains connected. 
Cabinet Layout
 WARNING
Failure to meet or exceed the minimum dimensions 
stated below may result in a fire hazard.
Carefully check the location where the range is to be 
installed. For best performance, the range should be 
placed away from drafts that may be caused by doors, 
windows and heating and air conditioning outlets.
To reduce the risk of personal injury and to reduce 
accumulated smoke in the room, Dacor strongly 
recommends installing a range hood. A range hood 
should project horizontally a minimum of five (5) inches 
beyond the face of the cabinets.
The range may be installed flush to the rear wall. 
Dacor highly recommends installing a non-combustible 
material on the rear wall above the range and up to the 
vent hood. It is not necessary to install non-combustible 
materials behind the range below the countertop height.
Regardless of the type of back wall surface, the range 
must not be installed or operated without the backguard 
in place.
**
** Cabinet depth is at discretion of customer 
but cabinet face MUST NOT protrude further 
than rear of front panel, see product dimesions
*** Consult local code for exact location 
requirements.
* Vertical to combustible surface
B
A
Non-Combustible 
surface along 
back wall
recommended
Suggested 
location of 
utilities***
30” (762mm)
min.*
A
B
30 1/16” 
(764mm)
36” (914mm) 
Recommended  
30” (762mm) 
Minimum
Cutout Dimensions