Thermador PRL366GH Installationsanweisungen

Seite von 64
English 12
Step 5:  Gas Requirements 
and Hookup
Verify the type of gas being used at the installation site. As 
shipped from the factory, units are configured for use 
with only natural gas or propane (LP) gas. Make certain 
the range matches the type of gas available at this 
location. These ranges are NOT convertible between 
different types of gas.
For installation of the appliance at high altitude, please 
consult your local gas company for their recommendation 
of the correct orifice sizes and any other necessary 
adjustments that will provide proper gas combustion at 
specified altitudes.
CAUTION
When connecting unit to propane gas, make 
certain the propane gas tank is equipped with its 
own high pressure regulator in addition to the 
pressure regulator supplied with the appliance. 
The pressure of the gas supplied to the 
appliance regulator must not exceed 14" (34.9 
mb) water column.
WARNING
Gas line must not come in contact with any 
components inside back cover of range. 
Hook Up
A manual gas shut-off valve must be installed external to 
the appliance, in a location accessible from the front, for 
the purpose of shutting off the gas supply. The supply 
line must not interfere with the back of the unit. Make 
sure the gas supply is turned off at the manual shut-off 
valve before connecting the appliance.
The range is supplied with its own pressure regulator 
that has been permanently mounted within the range 
body.
Use 3/4" flex line to connect between the gas supply 
and the appliance gas inlet, located at the lower right 
portion of the range. (See Figure 8.) The appliance inlet 
pipe connection is 1/2" NPT. Use caution to avoid 
crimping the 3/4" flex line when making bends. 
Suggested length of flex line is 48", however, please 
check local codes for your area's requirements before 
installation.
The gas supply connections shall be made by a 
competent technician and in accordance with local 
codes or ordinances. In the absence of local codes, the 
installation must conform to the National Fuel Gas Code 
ANSI Z223.1/NFPA54- current issue.
Always use pipe sealing compound or Teflon® tape on 
the pipe threads, and be careful not to apply excessive 
pressure when tightening the fittings.
L
eak testing of the appliance shall be in accordance with 
the following instructions.
Turn on gas and check supply line connections for 
leaks using a soap and water solution.
Bubbles forming indicate a gas leak. Repair all leaks 
immediately after finding them.
WARNING
Do not use a flame of any kind to check for 
gas leaks.
CAUTION:
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure testing 
of the gas supply piping system at test pressures 
equal to or less than 1/2 psig (3.5kPa.). 
The appliance and its individual shut off valve 
must be disconnected from the gas supply piping 
system during any pressure testing of the system 
at test pressures in excess of 1/2 psig (3.5kPa.). 
When checking the manifold gas pressure, the 
inlet pressure to the regulator should be at least 
6.0" (14.9 mb) W.C. for natural gas or 11.0" (27.4 
mb) for propane. 
Do not attempt any adjustment of the pressure 
regulator. 
Natural Gas Requirements:
Inlet Connection:
1/2" NPT internal
(Minimum 3/4" dia. flex line.) 
Supply Pressure:
6" min. to 14" max. water column.
(14.9 to 34.9 mb)
Manifold Pressure:
5" water column (12.5 mb)
Propane Gas Requirements:
Inlet Connection:
1/2" NPT internal
(Minimum 3/4" dia. flex line.) 
Supply Pressure:
11" min. to 14"max. water column.
(27.4 mb to 34.9 mb)
Manifold Pressure:
10" water column (24.9 mb)