APC MGE Galaxy 3500 40kVA 400V G35T40KH4B4S Benutzerhandbuch

Produktcode
G35T40KH4B4S
Seite von 40
5
MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
AC Output
Specifications
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type
5-wire (3PH + N + PE)
Output capacity
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
150% for 1 minute (battery operation)
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance
+/- 20% (304-477 V) at full load
Nom output current (A)
15.2
14.4
13.9
22.8
21.7
20.9
30.4
28.9
27.8
45.6
43.3
41.7
60.8
57.7
55.6
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal
Slew rate (Hz/Sec)
0.25-1
Total Harmonic Distortion (THD) < 1.5% linear
< 3.5% non-linear
Output power factor
0.8
Dynamic load response
+/- 5%
Output voltage regulation
+/- 1%
15 kVA
20 kVA
30 kVA
40 kVA
220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V
Connection type
3-wire (1PH + N + G)
Output capacity
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
150% for 1 minute (battery operation)
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance
+/- 20% (304-477 V) at full load
Nom output current (A)
68.4
65.0
62.6
91.2
86.6
83.5
136.7 129.9 125.2 182.3 173.2 166.9
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal 
Slew rate (Hz/Sec)
0.25-1
Total Harmonic Distortion 
(THD)
< 1.5% linear
< 3.5% non-linear
Output power factor
0.8
Dynamic load response
+/- 5%
Output voltage regulation
+/- 1%