MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
Battery Run-Times - Non-Modular Batteries
•  The below battery run-times are based on high quality batteries from approved manufacturers
•  The run-times are based on high rate batteries designed for UPS systems
•  The run-times are intended as a guide only, and APC disclaim the responsibility for these run-
times
10 kVA
15 kVA
Battery Ah
Load %
20 hr rate 
Ah
Approx. 
equivalent 
10 hr rate 
Ah
40
50
60
70
80
90
100
7.2
6.7
24
18
14
11
9
7
6
11
10
42
32
25
20
17
14
12
15
14
63
48
38
31
26
22
19
20
19
90
69
55
46
39
33
29
24
22
113
87
70
58
49
42
37
30
28
149
115
92
77
65
56
49
38
35
199
154
124
103
88
76
67
Battery Ah
Load %
20 hr rate 
Ah
Approx. 
equivalent 
10 hr rate 
Ah
40
50
60
70
80
90
100
11
10
25
19
14
11
9
7
6
15
14
38
29
22
18
15
13
11
20
19
55
42
33
27
23
19
17
24
22
70
53
42
35
29
25
21
30
28
92
70
56
46
39
34
29
38
35
124
95
76
63
53
46
40
50
47
174
133
107
89
75
65
57
0
10
20
30
40
50
60
70
80
90
100
110
120
40
60
80
100
Load %
R
u
nti
m
e
 [Mi
nute
s
]
2x16x12V/7.2(6.7)Ah
2x16x12V/11(10)Ah
2x16x12V/15(14)Ah
2x16x12V/20(19)Ah
2x16x12V/24(22)Ah
2x16x12V/30(28)Ah
2x16x12V/38(35)Ah
0
10
20
30
40
50
60
70
80
90
100
110
120
40
60
80
100
Load %
R
unti
m
e
 [M
inute
s
]
2x16x12V/11(10)Ah
2x16x12V/15(14)Ah
2x16x12V/20(19)Ah
2x16x12V/24(22)Ah
2x16x12V/30(28)Ah
2x16x12V/38(35)Ah
2x16x12V/50(47)Ah