MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
22
Cables
Recommended Cable Sizes
Note: Refer to IEC 60364-5-52 for installation methods. The recommended cable sizes are for 
installation method B2 and based on an environment with an ambient temperature of 30° C.
Note: Temperature ratings of conductors: 70°C. Use only copper conductors and PVC isolated 
cables.
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
Torque Specifications
The power wiring should be torqued to 7 Nm.
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
Utility/mains input
2.5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
Static bypass input
2.5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
DC input
50 mm
2
50 mm
2
50 mm
2
50 mm
2
50 mm
2
Output
2.5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
15 kVA
20 kVA
30 kVA
40 kVA
Utility/mains input
6 mm
2
10 mm
2
16 mm
2
25 mm
2
Static bypass input
25 mm
2
35 mm
2
70 mm
2
95 mm
2
DC input
50 mm
2
50 mm
2
50 mm
2
50 mm
2
Output
25 mm
2
35 mm
2
70 mm
2
95 mm
2