MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
26
Minimum Breaker Settings
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
Duration
800% overload 
bypass operation
150% overload 
normal/battery 
operation
125% overload 
normal/battery 
operation
Continuously
500 ms
60 s
10 min.
10 kVA
Mains input
-
1
-
-
16.4 A
Bypass input
121.5 A
-
-
16.7 A
Output
121.5 A
22.8 A
19 A
16.7 A
15 kVA
Mains input
-
1
-
-
24.6 A
Bypass input
182 A
-
-
25.1 A
Output
182 A
34.2 A
25.4 A
25.1 A
20 kVA
Mains input
-
1
-
-
32.5 A
Bypass input
244 A
-
-
33.4 A
Output
244 A
45.6 A
38 A
33.4 A
30 kVA
Mains input
-
1
-
-
49.1 A
Bypass input
364 A
-
-
50.1 A
Output
364 A
68.4 A
57 A
50.1 A
40 kVA
Mains input
-
1
-
-
65.6 A
Bypass input
487 A
-
-
66.9 A
Output
487 A
91.2 A
76 A
66.9 A
Note:1 For single mains systems, use the higher value of mains and bypass.
Duration
800% overload 
bypass operation
150% overload 
normal/battery 
operation
125% overload 
normal/battery 
operation
Continuously
500 ms
60 s
10 min.
15 kVA
Mains input
-
-
-
24.6 A
Bypass input
547 A
-
-
75 A
Output
547 A
103 A
86 A
75 A
20 kVA
Mains input
-
-
-
32.5 A
Bypass input
730 A
-
-
100 A
Output
730 A
137 A
114 A
100 A
30 kVA
Mains input
-
-
-
49.1 A
Bypass input
1094 A
-
-
150 A
Output
1094 A
205 A
171 A
150 A
40 kVA
Mains input
-
-
-
65.6 A
Bypass input
1459 A
-
-
200 A
Output
1459 A
274 A
228 A
200 A