Honeywell XL 800 SERIES Benutzerhandbuch

Seite von 36
Excel 800 
Troubleshooting 
 31 
EN1B-0410GE51 
R0908A 
Troubleshooting 
Testing Wiring Connections 
The push-in terminals feature small holes (1 mm in diameter) 
which can be used to measure the signals. 
► 
Insert a probe (1) as shown on the right. 
 
 
Fig. 49. Testing wiring connections 
 
Troubleshooting on the XCL8010AU Controller 
The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes: 
• 
Power LED (green) 
• 
Alarm LED (red) 
• 
L
ON
W
ORKS
 service LED 
• 
C-Bus Tx and Rx LEDs 
• 
HMI Tx and Rx LEDs 
 
Power LED (green) 
Table 37. XCL8010AU power LED 
case 
power LED 
meaning 
remedy 
1 ON 
Normal operation 
No action necessary 
2 Flashing 
One or more of the internal voltage supplies 
are outside of the permissible ranges. The 
controller stops operation. 
► 
Check power 
► 
Check wiring 
► 
If problem persists, replace hardware 
3 Goes 
out 
briefly 
•  The operator has activated the reset button 
•  The controller is performing a warm start 
No action necessary