If you want lower chilled water temperatures, you’ll need to mix 
process water with industrial- (not automotive) grade ethylene or 
propylene glycol with rust inhibitor to provide protection down to 
20°F (12ºC) below the operating temperature you want. Figure 3 
below shows the proper mixtures needed to provide protection to 
20°F (12ºC) below the operating temperature you want. You can 
then reset the freezestat cutout temperature to a temperature 10°F 
(6ºC) below the operating temperature you selected. 
 
 
Caution! 
Make sure all freezestat adjustments are performed 
by a qualified refrigeration service technician. 
 
The Sterling product warranty does not cover system freeze-up! 
 
 
Figure 3 
Freezing Protection Curve 
 
Ethylene glycol required for evaporator freeze protection
Ethylene
glycol
percent by
volume
Chilled water operating temperature ºF / ºC
60
50
40
30
20
10
0
-50ºF -40ºF
-40ºC
-30ºF -20ºF -10ºF 0ºF 10ºF 20ºF 30ºF 40ºF 50ºF 60ºF
16ºC
10ºC
4ºC
-1ºC
-7ºC
-12ºC
-18ºC
-23ºC
-29ºC
-34ºC
-46ºC