20
P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357
www.aprilairepartners.com
10009857   4 .12
B2205748A
U.S. Patent Number 8,146,376 (and other patents pending)
© 2012 Aprilaire – A division of Research Products Corporation
Thermal
Outdoor & Remote temperature sensor
Maximum distance: 300 feet
Room temperature measurement
Display range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurement
Display range: -20° to 130°F (-30° to 55°C)
Setpoint temperature range
Heat: 40° to 90°F (4° to 32°C) 
Cool: 50° to 99°F (10° to 37°C)
Setpoint humidity range
Humidification: 10% to 50% R .H . 
Dehumidification: 40% to 90% R .H .
SpECIfICATIONS
Electrical
Operating voltage
24VAC (18 – 30VAC)
Current
Maximum: 2.5A (total), 1.0A (single output) 
Maximum surge current: 5A
Power supply
Dual power . Can be battery or 24VAC powered .
When both the sources are available, battery will be used as 
back up power .
Battery power
Battery power: AA size alkaline battery x 2 
Battery life: Approximately 1 year
Environment
Temperature
Operating: 32° to 120°F (0° to 48.9°C) 
Shipping: -30° to 150°F (-34.4° to 65.5°C)
Relative humidity
Operating: 5% to 90% R .H . (non-condensing)