Honeywell MS4103 Benutzerhandbuch

Seite von 268
126
Unitary Valve
Vu52; Vu53
VU52; VU53
Two-way Fan Coil Valves, the VU53 
high pressure zone valves are used 
to control the flow of hot or chilled 
water in commercial HVAC 
equipment such as fan coil units, 
terminal reheat coils and 
convectors. 
IMPORTANT: These valves are not 
for use in systems containing 
dissolved oxygen.
SPECIFICATIONS
Valve Type ............................................ Fan Coil Valve
Valve Size  ............................................ 1/2; 3/4; or 1 in.
Connection Type  .................................. Sweat; NPT; or 
1/2 in. Inverted flare
Body Pattern  ........................................ Two-way, Straight-through
Flow Characteristic  .............................. Quick Opening
Controlled Medium ............................... Hot/Chilled Water with up to 
60% Glycol
Maximum Safe Operating Pressure  ..... 300 psig (2068 kPa) 
Ambient Temperature Range  ............... 34 F to 125 F at 200 F Fluid
(1 to 52 C @ 94 C Fluid) 
Actuation  .............................................. Must be purchased separately
Materials
(Body)  .................................................. Brass
(Stem) ................................................... Brass
(Seat) .................................................... Brass
(Plug/Ball/Disc)  .................................... Buna-N rubber
(Packing) .............................................. EPDM rubber
APPROVALS
Canadian Standards Association  ........ CSA C/US
FEATURES
• Compact construction for easy installation. 
• Fits under the cover of most baseboard convectors with 
actuator fitted to valve body. 
• VU52 and VU53 provide 2-way, straight-through control of 
water. 
• Available in normally closed (VU53) or normally open 
(VU52) configurations. 
• 300 psi (2,000 kPa, PN20) operating pressure rating. 
• Patented ball seal provides long service life, soft close off. 
• Triple O-ring seal provides three lines of defense against 
corrosion and water leakage around drive shaft. 
• Quick opening flow curve. 
• Available with NPT end connections for iron or steel piping.
DIMENSIONS DIAGRAM
2
1
VU52 AND VU53 VALVE WITH VU448 ACTUATOR
VU52 AND VU53 VALVE WITH ACTUATOR
VU ACTUATOR
2-3/8 
(60) 
7/8 DIA. 
(22) 
1-1/2 
(38) 
3-3/4 
(133) 
15/32 
(12) 
3/8 
(10) 
1-3/4 
(44) 
1-3/4 
(44) 
3/8 
(10) 
2-1/8 (54) 
(INVERTED  
FLARE) 
1-3/4 
(44) 
1-3/4 
(44) 
7/8 (22)
2-WAY
VALVE BODY SIZE 
A
1/2 IN. SWEAT 
1-5/6 (33)
3/4 IN. SWEAT 
1-3/8 (35)
1 IN. SWEAT 
1-11/16 (43)
1/2 IN. NPT 
1-3/8 (35)
3/4 IN. NPT 
1-11/16 (43)
HEIGHT NEEDED TO REMOVE ACTUATOR OR COVER
OPENING FOR 1/2 IN. CONDUIT ON OPPOSITE SITE OF
MANUAL LEVER FOR ALL MODELS.
M16818