Remote Trending (dial-up) 
General 
Per front-end (XBS, EBI), trend values for a total of 20 data points can be stored 
(via dial-up) in the remote trend buffer of the controller to which the modem has 
been connected. These 20 data points can come from the controller to which the 
modem has been connected, or they can come from various other controllers on 
the same C-Bus or L
ON
W
ORKS
 bus. 
 
 
Controller Firmware 2.03.xx and Higher 
Per front-end (XBS, EBI), trend values for a total of 100 data points can be stored 
(via dial-up) in the remote trend buffer of the controller to which the modem has 
been connected. These 100 data points can come from the controller to which the 
modem has been connected, or they can come from various other controllers on 
the same C-Bus or L
ON
W
ORKS
 bus. Unused application memory can be used as 
additional remote trend buffer. 
 
 
Controller Firmware 2.04.xx and Higher 
In combination with the large RAM controllers XD52-FC, XD52-FCS, XC5210C, a 
total of 384 KB of additional trend buffer is available. This increase in the trend 
buffer size reduces the number of times the controller must dial-up the front-end 
and lowers the risk of trend values being overwritten due to a full buffer. 
By exploiting this feature, it is possible, when no application is downloaded, to use 
the EXCEL controller as a pure trending device. 
The amount of additional memory available for the remote trend buffer is deter-
mined by the value for “Application Memory Size” entered with the MMI during the 
start-up sequence of the controller. This number is subtracted from the total 
application memory, and the resulting number, in Kbytes, is the additional remote 
trend buffer size. Fig. 24 illustrates the adjustable remote trend buffer. 
 
REMOTE TREND BUFFER
UNUSED APPLICATION MEMORY
e.g. 58 KB
    58 KB
= 1263 ADDITIONAL TREND SAMPLES
+ 100 TREND SAMPLES (DEFAULT)
= 1363 T0TAL TREND SAMPLES
1
2
8
 K
B
TOTAL APPLICATION MEMORY
APPLICATION
e.g. 70 KBYTES
 
Fig. 24. Adjustable remote trend buffer example 
 
The maximum number of trend values will be displayed on the MMI once a value for 
application memory size is entered. The adjustment range for the application 
memory size is the following: 
 
Table 22. Adjustment range for application memory size 
 
application memory size 
trend values in remote trend buffer 
maximum (default): 128 Kbyte 
42 per front-end 
example: 120 Kbyte 
100 per front-end 
minimum: 38 Kbyte 
100 per front-end; PLUS “N” for front-end A