Trane N512 Benutzerhandbuch

Seite von 84
Exhaust control
CNT-SVX07C-EN
41
fan configuration. The controller can be configured to auto, to a specific 
fan speed, or to off. If both a communicated and hard-wired value (fan-
speed switch) is present, the communicated value has priority. 
When the controller receives a communicated auto signal (or the associ-
ated fan-speed switch is set to 
AUTO
 with no communicated value 
present), the fan will operate in the auto mode. In the auto mode, the fan 
will operate according to the fan default (configurable using the Rover 
service tool). The fan speed can be configured to default to auto, a specific 
speed, or off for both heating and cooling operation.
Configured as auto and with multiple speeds available, the fan will auto-
matically switch speeds depending on the difference between the zone 
temperature and the active zone temperature setpoint. The fan speed will 
increase as the difference increases and decrease as the difference 
decreases.
When the controller receives a communicated fan-speed signal (high, 
medium, low) or the associated fan-speed switch is set to a specific fan 
speed, the fan will run continuously at the desired fan speed during occu-
pied, occupied standby, and occupied bypass operation. During unoccu-
pied operation, the fan will cycle between off and high regardless of the 
communicated fan-speed signal or fan-speed switch setting (unless either 
of these is off, which will control the fan off).
The fan will turn off when the controller receives a communicated off sig-
nal, when the fan-speed switch is set to 
OFF
, when specific diagnostics are 
generated, or when the default fan speed is set to off and the fan is oper-
ating in the auto mode.
The ability to enable or disable the controller’s associated fan speed 
switch is configurable.
Exhaust control
Exhaust control is accomplished by a single-speed exhaust fan or a two-
position exhaust damper. BOP2 controls this function. To enable exhaust 
control, configure the controller by selecting Exhaust Fan/Damper 
Present and by selecting the number of fan speeds as either One or Two.
The exhaust function is coordinated with the supply fan and outdoor/
return air dampers as follows:
The exhaust output is energized only when the supply fan is operat-
ing and the outdoor air damper position (%) is greater than or equal 
to the Exhaust Fan/Damper Enable Setpoint (configurable using the 
Rover service tool). 
Note:
In occupied mode, The Tracer ZN521 zone controller requires 
continuous fan operation because of cascade zone control. In 
unoccupied mode, the fan cycles.