Installation / 
Assemb
ly
7
2009 G3, G4, G5 Grills
LTR20091050, Rev. A
www.calspas.com
The maximum fuel capacity is 20 lbs. of propane, or 5 gallons.  Full 
cylinder  weight  should  be  approximately  38  lbs.  (43.7  lbs.  nominal 
water capacity.) Never fill the cylinder beyond 80% full.
Place the dust cap on the cylinder valve outlet whenever the cylinder is 
not in use. Only install the type of dust cap on the cylinder valve outlet 
that is provided with the cylinder valve. Other types of caps or plugs 
may result in leakage of propane.
LP Gas Hook Up
An enclosure for an LP gas cylinder shall be vented by openings at the 
level of the cylinder valve and at floor level. The effectiveness of the 
openings for purposes of ventilation shall be determined with the LP-
gas supply cylinder in place.  This shall be accomplished in one of the 
following manners:
One side of the enclosure shall be completely open.
1. 
Enclosures that have four sides, complete with a top and bottom:
2. 
At least two ventilation openings at cylinder valve level shall be 
a. 
provided in the sidewall, equally sized, spaced at 180º (3.14 
rad), and unobstructed. Each opening shall have a total free 
area of not less than one square inch per pound (7.1 cm²/kg) 
of stored fuel capacity, and not less than a total free area of 10 
square inches (64.5 cm²).
Ventilation openings shall be provided at floor level and shall 
b. 
have  a  total  free  area  of  not  less  than  one  square  inch  per 
pound (7.1 cm²/kg) of stored fuel capacity and not less than 
a total free area of 10 square inches (64.5cm²).  If ventilation 
openings at floor level are in a sidewall, there shall be at least 
two openings.  The bottom of the openings shall be at floor 
level  and  the  upper  edge  no  more  than  5  inches  (127  mm) 
above the floor. The openings shall be equally sized, spaced at 
180º (3.14 rad) and unobstructed.
Every opening shall have minimum dimensions so as to permit 
c. 
the entrance of a 1/8 inch (3.2 mm) diameter rod.
Transporting and Storing LP Gas
Transport only one cylinder at a time. Ensure the cylinder is secured in 
an upright position with the control valve turned off and the dust cap 
in place. Store cylinders outdoors and out of reach of children. Do not 
store cylinders in a building, garage, or any other enclosed area.