Communication Guide
Bus connection through a SCA type junction box 
1. Master (PLC, PC or communication module)
2. Modbus cable (It is different according to the master side or a master having polarization combined to the other part of Bus) 
3. Junction box
4. Modbus cable
5. Line terminators : 120
Ω
- 0.25W 
Please use a cable with 2pair shieded twisted conductors for Interface protection.  
It is adviced to isolate the Modbus cable 30cm(11.8in) at least  from a power cable. 
If necessary, intersect the Modbus cable to a power cable perpendicularly. 
Refer to the diagram in the left side for the line terminator wiring.
2 wire MODBUS RJ45 connections
Pin ‘S’ can be used for shield wire connection.
Pin on RJ45
Pin on nEOCR
EIA/TIA 485 name
4
D1
B/B’
5
D0
A/A’
8
V-
C/C’