Note 1:
Assume that the inverter current rating is 1000 (for D002).
The following table lists holding registers for the “D” Group Monitor Functions.
Note 1:
Stores new data made by transmission (for Write all memory). For more 
information, refer to the Store New Register Data (ENTER command).
Holding Registers, “D” Group Monitor Functions
Func. 
Code
Name
R/W
Description
Network Data
Reg.
Res.
D081
Trip monitor 1
R
Trip monitor 1: factor code
0100h
R
Frequency
0101h
0.1 Hz
R
Current
0102h
0.1 %
R
Voltage
0103h
0.1 V
R
Run time (high)
0104h
1. h
R
Run time (low)
0105h
R
ON time (high)
0106h
1. h
R
ON time (low)
0107h
D082
Trip monitor 2
R
Trip monitor 1: factor code
0108h
R
Frequency
0109h
0.1 Hz
R
Current
010Ah
0.1 %
R
Voltage
010Bh
0.1 V
R
Run time (high)
010Ch
1. h
R
Run time (low)
010Dh
R
ON time (high)
010Eh
1. h
R
ON time (low)
010Fh
D083
Trip monitor 3
R
Trip monitor 1: factor code
0110h
R
Frequency
0111h
0.1 Hz
R
Current
0112h
0.1 %
R
Voltage
0113h
0.1 V
R
Run time (high)
0114h
1. h
R
Run time (low)
0115h
R
ON time (high)
0116h
1. h
R
ON time (low)
0117h
Write all memory
W
Infinite  *1
0900h