DCS -VH-48HS Benutzerhandbuch
Duct Information
10
GENERAL
-
When planning the path for ducting to the outside, keep in
mind the following guidelines:
mind the following guidelines:
-
Minimize use of elbows and transitions in ductwork as to
maximize air flow to outside of building. An efficient airflow
path contributes to the overall efficiency of the Vent Hood.
maximize air flow to outside of building. An efficient airflow
path contributes to the overall efficiency of the Vent Hood.
-
DCS recommends the use of smooth wall ducting, not
flexible ductwork.
flexible ductwork.
-
Transitions are required from rectangular to round ducting
DCS-IB12 BLOWER Requires one of the following 4-1/2” x 18” to 10” round transitions
(purchase separately)
Model 19052-01-Vertical discharge
Model 19052-02-Rear discharge
Model 19052-03-Left discharge
Model 19052-01-Vertical discharge
Model 19052-02-Rear discharge
Model 19052-03-Left discharge
-
Duct tape may be used at ducting joints.
DCS VH 48 / DCS VH12 36 REQUIREMENTS
-
DCS recommends the use of 10” round ducting which provides 78.6 sq. In. of surface area.
-
Alternate duct sizes in rectangular style may be used. If a rectangular duct style is used, the duct
must equal at least 78.6 sq. In. for best results. (Example- 3-1/4” x 24” duct = 78 sq. In.)
must equal at least 78.6 sq. In. for best results. (Example- 3-1/4” x 24” duct = 78 sq. In.)
-
Maintain consistent ducting square area as to avoid reduced air flow. [ie.- With a VH-48 Hood,
connecting a 4”x13” (52 sq. In.) to a 10” round (78.6 sq. In.) is not recommended]
connecting a 4”x13” (52 sq. In.) to a 10” round (78.6 sq. In.) is not recommended]
DCS VH 36/30 REQUIREMENTS
-
DCS recommends the use of 7” round ducting which provides 34.7 sq. In. of surface area.
-
Alternate duct sizes in rectangular style may be used. If a rectangular duct style is used, the duct
must equal at least 34.7 sq. In. for best results.
must equal at least 34.7 sq. In. for best results.
DUCT ACCESSORIES
-
Wall Caps and Roof Caps must have free open area equal to duct size diameter.
-
Note that a Sealed Back Draft Damper may reduce air delivery.
10"
10-1/2"
4-5/8"
Vertical Duct Transition
18-5/8"
11"