Greenheck Fan DFD-M210 Benutzerhandbuch

Seite von 6
Application
Model DFD-M210 is a multi-blade fire damper with 3V style blades. 
The DFD-M210 has been qualified to 10.2 m/s (2000 fpm) and 1.0kPa  
(4 in. wg.) for operation and dynamic closure in emergency fire 
situations. Model DFD-M210 may be installed vertically (with blades 
running horizontal) or horizontally and is rated for airflow in either 
direction.
Model DFD-M210 has also been tested in accordance with BS476 to 
4 hours at Warrrington Fire, UK, and is approved for fire partitions of 4 
hours or less where British Standards are required. 
Ratings
UL 555 Fire Resistance Rating 
 
Fire Rating: 
1
1
2
 Hours 
 
Dynamic Closure Rating:  Actual limits are size dependent 
 
Maximum Velocity: 
10.2 m/s (2000 fpm) 
 
Maximum Pressure: 
1 kPa (4 in. wg)
BS476 Fire Resistance Rating 
 
Fire Rating: 
4 hours
Standard Construction
 
Frame:  
127mm x 25 mm (5 in. x 1 in.) 1.5mm 
 
 
(16 gauge) galvanized steel hat 
 
 
channel with reinforced corners. A 
 
 
low profile head and sill are used on 
 
 
sizes less than 432mm (17 in.) high to 
 
 
 maximize free area and performance. 
 
Blades:  
1.5mm (16 gauge) galvanized steel, 
 
 
reinforced with 3 longitudinal 
 
 
structurally designed vee’s. 
 
Seals: 
Flexible stainless steel jamb seals. 
 
Linkage: 
Concealed in jamb. 
 
Fusible Link: 
UL listed 74ºC (165°F) 
 
Axles: 
13mm (
1
in.) dia. plated steel. 
 
Bearings: 
Bronze sleeve type. 
 
Actuator: 
Manual quadrant.
Size Limitations
 
Minimum Size: 
203mm W x  152mm H 
 
 
(8 in. W x 6 in. H) 
 
Maximum Size: 
 
Single Section: 
914mm W x 914mm H 
 
 
(36 in. W x 36 in. H) or 
 
 
813mm W x 1270mm H 
 
 
(32 in. W x 50 in. H) 
 
Multi Section: 
1626mm W x 1270mm H 
 
 
(64 in. W x 50 in. H)
Optional Features
•100ºC (212°F), 141ºC (286°F), and 177ºC (350°F) fusible links (UL only)
• 69°C (155°F) fusible links (BS476)
• Factory mounted sleeves
• Retaining angles
• Sleeve with integral flange on both sides
Model DFD-M210
Multi-Blade 
FIRE DAMPER
Steel 3V Blades
UL555 1
1
/
2
 Hour Fire Resistance Rating
4 hour Fire Resistance Rating (BS476)
* W & H dimensions furnished approximately 6mm (
1
/
in.)  undersize.
  (Add sleeve thickness for overall sleeved damper dimension)
H
W
LH
RH
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 (Listing #R13317)
Model DFD-M210 is intended for installation in 
accordance with fire damper requirements 
established by:
National Fire Protection Association 
NFPA Standards 80, 90A & 101
ICBO  Uniform Building Codes
IBC  International Building Codes  
SBCCI  Standard Building Codes
British Standard BS476 
Tested to 4 hours at Warrington Fire, UK
R
Greenheck Kunshan Co. Ltd. and Greenheck Fan 
Corporation certifies that the model DFD-M210 
shown herein is licensed to bear the AMCA 
Seal. The ratings shown are based on tests and 
procedures performed in accordance with AMCA 
Publication 511 and comply with the requirements 
of the AMCA Certified Ratings Programs. The 
AMCA Certified Ratings Seal applies to air 
performance ratings only.