Amana HRV-300D Benutzerhandbuch

Seite von 28
23
TROUBLESHOOTING
Solutions
Causes
Problem
Dehumidistat control is set too low
Dehumidistat control is set too high
Sudden change in temperature
Storing too much wood for heating
Dryer vent exhaust is inside home
Poor air circulating near windows
Well sealed basement door is closed
Improper adjustment of dehumidistat con-
trol
Air is too dry
Air is too humid
Persistent condensation 
on window
Increase the desired level of humidity. Change ventilation mode from
continuous mode to standby.
Balance HRV
Reduce the desired level of humidity. Combine this step with use of con-
tinuous exchange mode.
Wait until outside temperature stabilizes (winter). Heating will also
improve situation.
Store a majority of your wood outside. Even dried, a cord of wood con-
tains more than 20 gallons of water.
Arrange outside vent for dryer.
Open curtains or blinds. Bay or bow windows may require mechanical
method.
Balance HRV
Open the door or install a grill on the door.
Reduce the desired level of humidity. Combine this with the use of con-
tinuous exchange mode.
Balance HRV
-Clean exterior hoods or vents
-Remove and clean filter
-Remove and clean core
-Check and open grilles
-Have electrician check supply voltage at house
-Check duct installation
-Increase the speed of the HRV/ERV
-Have contractor balance HRV/ERV
-Locate the grilles high on the walls or under the baseboards, install
ceiling mounted diffuser or grilles so as not to directly spill the supply
air on the occupant (eg. Over a sofa)
-Turn down the HRV/ERV supply speed.  A small duct heater (1kw)
could be used to temper the supply air
-Placement of furniture or closed doors is restricting the movement of
air in the home
-If supply air is ducted into furnace  return, the furnace fan may need to
run continuously to distribute ventilation air comfortably
-Note: minimal frost build-up is expected on cores before unit initiates
defrost cycle functions
-Have HVAC contractor balance the HRV
-Tape and seal all joints
-Tape any holes or tears made in the outer duct covering 
-Ensure that the vapor barrier is completely sealed.
-1/4” (6mm) mesh on the outside hoods
is plugged
-Filters  plugged
-Core obstructed 
-House grilles closed or blocked
-Dampers are closed if installed
-Poor power supply at site
-Ductwork is restricting HRV/ERV
-Improper speed control setting
-HRV/ERV airflow improperly balanced
Poor Air Flows
-Poor location of supply grilles, the airflow
may irritate the occupant 
-Outdoor temperature extremely cold
Supply air feels cold
-HRV air flows are improperly 
balanced
-Malfunction of the HRV defrost 
system
HRV and / or Ducts
Frosting up
-Incomplete vapor barrier around 
insulated duct
-A hole or tear in outer duct covering
Condensation or Ice
Build Up in Insulated
Duct to the Outside
HRV out of balance
HRV out of balance
HRV out of balance