Greenheck Fan OFSD-312 Benutzerhandbuch

Seite von 6
Application
Model OFSD-312 is an ‘out of the wall’ high performance combination 
fire smoke damper with class II leakage. OFSD-312 is approved for 
use in walls, partitions, and floors with fire resistance ratings less than 
3 hours. Removal of wall grille allows access to actuator and other 
components. High strength airfoil blades insure the lowest resistance 
to airflow in HVAC systems with velocities to 3000 fpm (15.2 m/s) 
and pressures to 4 in. wg  (1 kPa). Model OFSD-312 shall be installed 
vertically (with blades running horizontal) or horizontally and is rated 
for airflow and leakage in either direction.
Ratings
UL555 Fire Resistance Rating: 
 
Fire Rating:  
1
1
2
 
hours in walls  
 
Dynamic Closure Rating: Actual ratings are size dependent 
 
Max. Velocity: 
up to 3000 fpm (15.2 m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa) - differential pressure 
UL555S Leakage Rating: 
 
Leakage Class: 
 
Operational Rating: 
Actual ratings are size dependent 
 
Max. Velocity: 
up to 3000 fpm (15.2m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa)
 
Max. Temperature: 
350ºF (177ºC)- depending upon the 
 
 
actuator
Standard Construction
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile 
 
 
head and sill are used on sizes less 
 
 
than 17 in. (432mm) high. 
 
Blades:  
Double skin airfoil shape of 
 
 
galvanized steel with full length 
 
 
structural reinforcement. 14 ga. 
 
 
(2mm) equivalent thickness. 
 
Seals: 
Extruded silicone rubber blade seals. 
 
 
Flexible stainless steel jamb seals. 
 
Linkage: 
Concealed in jamb 
 
Fusible Link: 
RRL 165°F (74ºC) 
 
Axles: 
1
2
 in. (13mm) dia. plated steel 
 
Bearings: 
Bronze sleeve type 
 
Sleeve: 
Galvanized; wrapped with thermal 
 
 
blanket
Size Limitations:
 
Minimum Size:  
12 in.W x 12 in. H 
 
 
(305mm x 305mm) 
 
Maximum Size: 
 
Single section: 
32 in. W x 30 in. H 
 
 
(813mm W x 762mm H)
 
Multiple Section: 
36 in.W x 36 in. H 
 
 
(914mm x 914mm)
Optional Features:
•  POC retaining Angles
•  RRL/OCI (open closed indication switches)
•  165ºF (74ºC), 212ºF (100ºC), 250ºF (121ºC), 350ºF (177ºC) RRL’s
available
• TOR (remote override allows damper to perform smoke
management functions during fire emergency.)
•  Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Smoke detectors
• Momentary switch
• PRV (pneumatic relief valve)
• Security bars
•Sealed transition and sleeves
Model OFSD-312
Out of Wall Combination Fire Smoke Dampers
Steel Airfoil Blades
UL 555S Leakage Class I
UL555 1
1
2
 Hour Fire Resistance Rating
Horizontal or Vertical Mount
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317)
*  W & H dimensions furnished approximately 
1
4
 in. (6mm) undersize. 
Add blanket thickness (
1
8
 in.[3mm]) and sleeve thickness for 
overall sleeved damper dimension) 
Oversize wall opening as follows: 
Nominal damper size plus 
3
8
 in.(9.5mm) (see Page 6)
R
Greenheck Fan Corporation certifies that the 
model OFSD-312 shown herein is licensed to 
bear the AMCA Seal. The ratings shown are 
based on tests and procedures performed in 
accordance with AMCA Publication 511 and 
comply with the requirements of the AMCA 
Certified Ratings Programs. The AMCA Certified 
Ratings Seal applies to air performance ratings 
only.
Model OFSD-312 meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC  International Building Codes
ICBO  Uniform Building Codes
CSFM California State Fire Marshal 
  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
Installation instructions available at www.greenheck.com