P L A N N I N G A N D D E S I G N G U I D E
V I K I N G R A N G E . C O M
1 - 8 8 8 - V I K I N G 1
R E L E A S E D 0 5 / 1 2 / 0 8
© 2 0 0 7 V R C — INFORMATION SUBJECT TO CHANGE
VENTILATION
Built-In Custom Ventilator Systems
Proper installation/ ducting is
extremely important to ensure
maximum performance. Use a qualified
and trained installer.
DUCTING
• Check with a qualified and
trained installer or local codes
for makeup air requirements, if
any.
• Max. duct run length
o For 300 – 1,200 CFM—
50’ (152.4 m)
o For 1,500 CFM—75’ (22.9 m)
o Duct run length is for
general reference only;
always use a qualified and
trained installer.
o Straight runs and gradual
turns are best; for example,
each 90° elbow is equivalent
to 5’ – 10’ (1.52 – 3.05 cm)
of straight run.
• 7” (17.8 cm) round duct for
300 – 600 CFM; 10” for 900 –
1500 CFM
o Never use flexible duct; it
creates back pressure/air
turbulence and greatly
reduces performance.
GAS
Not applicable
ELECTRICAL
• Hardwire direct with two-wire
ground
• 120 VAC/60 Hz
• Max. amp usage (rating
includes recommended
ventilator kit rating)—see
Installation Requirements
table
PLUMBING
Not applicable
Installation Requirements
Model
Ventilator Kits
Duct Size
Max. Amps
Interior
Exterior
Interior
Exterior
Interior
Exterior
VBCV3038
VIV300/600/1200*
VEV900/1200*
7” (17.8 cm)/
10” (25.4 cm)
5.0/6.2/8.7
8.7/6.1
10” (25.4 cm)
VBCV3638
VIV300/600/1200*
VEV900/1200*
7” (17.8 cm)/
10” (25.4 cm)
5.0/6.2/8.7
8.7/6.1
10” (25.4 cm)
VBCV4238
VIV600/1200*
VEV900/1200*
7” (17.8 cm)/
10” (25.4 cm)
6.2/8.7
8.7/6.1
10” (25.4 cm)
VBCV4838
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
11.1
8.4/9.1
VBCV5438
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
11.1
8.4/9.1
VBCV6038
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
11.5
8.8/9.5
VBCV6638
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
11.5
8.8/9.5
VICV3698
VIV600/VIV1200*
VEV900/1200*
7” (17.8 cm)
10” (25.4 cm)
4.9/7.4
7.4/4.7
VICV4298
VIV600/1200*
VEV900/1200*/1500
7” (17.8 cm)
10” (25.4 cm)
4.9
7.4/4.8/5.4
VICV5498
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
8.2
5.6/6.2
VICV6698
VIV1200*
VEV1200*/1500
10” (25.4 cm)
10” (25.4 cm)
9.0
6.3/7.1
DBCV3082
DIV300/440
DEV900**/1200*
7” (17.8 cm)
10” (25.4 cm)
1.7/3.2
6.6/3.9
DBCV3682
DIV300/440
DEV900**/1200*
7” (17.8 cm)
10” (25.4 cm)
1.7/3.2
6.6/3.9
DBCV4282
DIV440
DEV900**/1200*
7” (17.8 cm)
10” (25.4 cm)
3.2
6.6/3.9
DBCV4882
DIV880
DEV1200/1500
10” (25.4 cm)
10” (25.4 cm)
5.6
4.3/5.1
DICV3632
DIV440
DEV900**/1200*
7” (17.8 cm)
10” (25.4 cm)
4.0
7.5/5.2
DICV4232
DIV440
DEV900**/1200/1500
7” (17.8 cm)
10” (25.4 cm)
4.0
7.5/5.2/6.0
DICV5432
DIV880
DEV1200/1500
10” (25.4 cm)
10” (25.4 cm)
6.4
5.2/6.0
*1200 CFM interior and exterior (if applicable) ventilator should be used with all outdoor approved models and when indoor models are installed over
ranges/rangetops with gas grill.
**Must use 8” duct from canopy to ceiling – trasition to 10” duct past duct cover.
Note: Exhaust capacity based on tests with 0.1 static pressure. Without applying static pressure (some brands do not), CFM could be
greatly overstated.
UTILITY REQUIREMENTS