Lifebreath RNC95 Benutzerhandbuch

Seite von 36
27
Air Flow Balancing using the Door Ports
Models RNC155 and RNC200 Only
The door ports ( MODELS RNC155 & RNC 200) are designed
to quickly and measure the airflows for balancing. 
Normally the HRV would be balanced on high speed. If the
HRV is connected to a forced air system, both systems should be
set to run at the highest operational speed when balancing is
performed. 
Balancing Procedure
Step 1
Remove balancing port covers.
Step 2
Insert one end of each connection hose into a rubber 
fitting. (Use light pressure until fitting is snug).
Step 3
Attach the connection hoses to pressure gauge
Step 4
Fresh Air - Connect hoses to door ports as illustrated
(record reading).
Step 5
Stale Air - Connect hoses to door ports as illustrated
(record reading).
Step 6
Refer to the Airflow Reference Chart for the conversion
of gauge reading to airflow reading.
Step 7
Damper the airflows as required to balance the system.
The fresh airflow must equal the stale airflow.
Step 8
Repeat steps 4 to 7 as required to confirm airflows.
Magnehelic Door Port Balancing Kit
Part No. 99-206
Use the Magnehelic Gauge Kit (Part No. 99-206) for door port
balancing.
1 - Pressure Gauge
4 - Rubber Fittings
2 - Connection Hoses
1 - Instruction Page
Fresh Air
Step 4
Measuring Fresh Air Side (Connect to both ports at the same time).
MAGNEHELIC
Pressure
Gauge
MAGNEHELIC
Pressure
Gauge
Stale Air
Step 5
Measuring Stale Air Side (Connect to both ports at the same time).
Pressure Gauge 
Reading
Fresh Air 
Stream Flow
Stale Air 
Stream Flow
(in w.g.)
(cfm)
(cfm)
0.070
75
54
0.080
80
59
0.090
84
65
0.100
89
70
0.110
93
75
0.120
98
81
0.130
102
86
0.140
106
91
0.150
111
97
0.160
115
102
0.170
120
114
0.180
124
118
0.190
128
123
0.200
133
128
0.210
137
133
0.220
142
138
0.230
146
143
0.240
151
148
0.250
155
153
0.260
159
158
0.270
164
163
0.280
168
167
0.290
173
172
0.300
177
177
0.310
181
182
0.320
186
187
0.330
190
192
0.340
195
197
Airflow Reference Chart