Cornelius CCM0530 Benutzerhandbuch

Seite von 129
 
 
 Refrigeration System 
Page E1 
 
Refrigerant Cycle and 
Components 
Before diagnosing the refrigeration 
system, it is very important that the 
refrigerant charge be correct.  
Whenever the refrigeration system 
has been opened, the filter-drier 
must be replaced and the proper 
refrigerant charge must be weighed 
in.  See refrigerant charge data on 
page A5–A8
 
Refrigerant Pressures 
The suction pressure at the 
beginning of the freeze cycle can vary +/- 10 psi 
 (.7 bar) depending on operating conditions.  Reference Chart on page E10-E13.   Pressures less 
than this may indicate an undercharge.  The discharge pressure on water-cooled units should be 
250 psi (17.01 bar) for R404a units.  The discharge pressure on air cooled units will vary with 
ambient conditions but will typically run higher than water cooled units.  Remote condensers 
located in ambient temperatures below 70°F (21°C) will typically run a lower discharge pressure.  
See Mixing Valve later in this section.  
 
Refrigerant in a gas state is pumped throughout the refrigeration system by a hermetic 
compressor to the condenser.  Heat is removed from the refrigerant either by forced air 
movement through an air-cooled condenser or transferring heat from the refrigerant to water 
through a water-cooled condenser.  The refrigerant changes to a liquid when cooled. 
 
The refrigerant in a liquid state passes through a filter drier.  The filter drier traps 
small amounts of moisture and foreign particles from the system.  The filter drier must 
be
 replaced whenever the refrigeration system is opened or if the refrigerant charge 
has been completely lost. 
  
Compressor 
The compressor runs during the entire cycle.  If the valves in the 
compressor are damaged, the compressor will be unable to pump 
refrigerant efficiently.  Damaged valves are usually the result of another 
problem in the refrigeration system such as liquid refrigerant returning to 
the compressor, oil slugging or high head pressure.  When a compressor 
is replaced it is important that the refrigerant charge be weighed in and 
the system checked for proper operation to prevent a repeat failure. 
 
An inefficient compressor will usually have a higher than normal suction 
pressure at the end of the cycle.  The freeze cycle will be longer than normal and/or the harvest 
cycle may be excessively long.  Check the compressor amperage draw 5 minutes into the freeze 
cycle.  If the compressor amp draw (Reference data plate on ice machine back panel) is less than 
70% of rated full load amps, the compressor may be inefficient.  These symptoms may also be 
caused by other problems, therefore it is important to use the troubleshooting trees when 
diagnosing a problem.  See Electrical System for more information on the compressor and 
compressor start components.