Installation Instructions
Connecting to a Three Wire Electrical 
System - Where Local Codes Permit
 WARNING
Do not connect the green appliance conduit wire to the 
neutral (white) junction box wire unless local building 
codes permit.
Separate the wires coming out of the appliance conduit.
1. 
Connect the green and white wires from the appliance 
2. 
conduit to the white (neutral) supply wire in the junction 
box.
Connect the black wire from the appliance conduit to 
3. 
the black (L1) supply wire in the junction box.
Connect the red wire from the appliance conduit to the 
4. 
red (L2) supply wire in the junction box.
Conduit from 
appliance 
Cable from 
power supply 
Wire nut
(3 places)
Junction
box
RED 
RED 
GREEN 
WHITE 
WHITE 
BLACK 
BLACK 
Connecting to a Three Wire Electrical 
System with External Ground - Where Local 
Codes Permit
 WARNING
Do not connect the green appliance wire to the junc-
tion box or to a cold water pipe unless local building 
codes permit.
Do not ground the appliance to a gas supply pipe or 
hot water pipe.
If connecting the ground wire to a grounded cold 
water pipe, connect using a separate copper 
grounding wire (No. 10 minimum) and a clamp with 
an external grounding screw. The grounded cold 
water pipe must have metal continuity to electrical 
ground and must not be interrupted by insulating 
materials. Any insulating materials must be jumped, 
with a minimum, 4 AWG wire to establish continuity 
to ground.
 NOtE
If the junction box has been properly grounded by a 
licensed electrician, the green (ground) wire from the 
appliance conduit may be connected to the junction box 
using a loop terminal.
See the diagram on the following page. To connect the 
green appliance conduit wire to a grounded cold water 
pipe:
Separate the wires coming out of the appliance conduit.
1. 
Connect the white wire from the appliance conduit to 
2. 
the white (neutral) supply wire in the junction box.
Connect the black wire from the appliance conduit to 
3. 
the black (L1) supply wire in the junction box.
Connect the red wire from the appliance conduit to the 
4. 
red (L2) supply wire in the junction box.
Connect the green wire from the appliance conduit to a 
5. 
grounded cold water pipe as shown. Jumper any insu-
lating materials as shown above with a length of No. 4 
copper wire. Securely clamp the wire to bare metal at 
both ends.
Conduit from 
appliance 
Cable from 
power supply 
Wire nut
(4 places)
Junction
box
RED 
RED 
GREEN 
GREEN 
WHITE 
WHITE 
BLACK 
BLACK 
Separate No. 10 (minimum) 
copper grounding wire 
Clamp must be 
tight on pipe 
No. 4 
copper wire 
Metal 
water pipe 
Clamps
Bare metal
Meter