ULTRAMATRIX E-SERIES MANUAL
 
16 
d.  Select “System” and press [Enter].   
e.  Next, select “Starting computer number” and press [Enter].  An 
input box will display for a new starting computer number.  
Enter the correct “Starting computer” number for this Unit (See 
page 15) and press [Enter]. 
f. 
Press the “Esc” key to return to the “Main menu”. 
g.  Select “Save” and press [Enter]. A “YES/NO” choice box will 
display.  Select “YES” and press [Enter] to save the changes. 
h.  Turn the power off on the UltraMatrix. 
i. 
Connect the KVM station to the KVM #1 connector on Unit #3. 
j. 
Configure this Units “Starting computer” number and then all 
other Units in the system.  When the “Starting computer” 
number has been entered for all Units, proceed to step 3. 
3.  Connect the KVM station to Unit #1’s KVM #1 connector and apply 
power to the monitor and Unit #1. 
4.  Enter the “Maximum computers” number 
a.  Display the main menu (left control [Ctrl] key, then the F12 key.) 
b.  Select “System” and press [Enter]. 
c.  Select “Maximum computers” and press [Enter].  An input box 
will display for a new “Maximum computers” number.  Enter the 
correct “Maximum computers” value as explained on page 15 
and press [Enter]. 
d.  Press the “Esc” key to return to the “Main menu”, select “Save” 
and press [Enter]. A “YES/NO” choice box will display.  Select 
“YES” and press [Enter] to save the change. 
5.  The next item is to connect the Units in a “BUS” configuration and 
verify that communication between the Units is established.  To do 
this, call up the System status display by pressing and releasing 
the left control [Ctrl] key, then the F12 key.   
6.  Select “Status” from the Main menu and press [Enter].  The system 
status screen will display showing the following: (Figure 14)  
a. Computers  
b.  Power (Power on status) 
c.  POS (Card position) 
d.  VER (Program version) 
e. KVM 
f. CPU 
g. User 
h. Status 
 
The number of system CPU ports that Unit #1 has will be 
highlighted.  If the Unit is a 16-port switch, computers 1–4, 5–8, 
9–12, and 13–16 will be highlighted on the status screen.  
(Note: “System CPU ports” = total RS232 ports times 4)