Installation and Configuration
14
6.3
Connect Input/Output Power
The UPS has hardwire terminal blocks for input and output electrical connections. Optional output 
distribution modules permit connecting additional loads to the UPS. These optional plug-and-play 
distribution modules offer different types and numbers of connection plugs.
6.3.1 Distribution Module Electrical Connections
Electrical connections are made through a removable conduit box that attaches to the rear of the 
UPS.
The installer must provide a 60A branch circuit breaker. The input circuit breaker and the output cir-
cuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and 
the distribution box.
The manual bypass switch passes utility power directly to the bypass switch from the input terminal 
block. The input circuit breaker does not disconnect power from the manual bypass switch.
Figure 6
60A branch circuit breaker connection diagram
!
WARNING
The UPS must be completely powered down before beginning to make these electrical 
connections.
!
CAUTION
A disconnect switch shall be provided by others for ac input circuit. To reduce the risk of fire, 
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes 
rating in accordance with the National Electric Code, ANSI/NFPA 70.
!
CAUTION
A disconnect switch shall be provided by others for ac output circuit. To reduce the risk of fire, 
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes 
rating in accordance with the National Electric Code, ANSI/NFPA 70.
Optional
Output
Distribution
Plate
Utility
Input
60A External 
Branch
Circuit Breaker
60A 
Input
Circuit
Breaker
Output
Terminal
Block
60A 
Output
Circuit
Breaker
60A Maintenance 
Bypass Breaker
UPS
Input 
Indicator
Output 
Indicator