Communications
32
11.0 C
OMMUNICATIONS
11.1 Communications Interface Port
The Liebert GXT2-10000RT208 UPS has a standard DB-9 serial port female connector located on the 
rear of the UPS unit. Several signals are provided on this port and are assigned as follows:
11.1.1 DB-9 Interface Port
Using the following directions to attach the smaller enclosed ferrite 
bead clamp to the communication cable as shown at right:
1. Open the ferrite bead.
2. Place the communication cable inside the ferrite bead groove.
3. Position the ferrite bead as close as possible to the end of the cable 
that connects to the DB-9 connector of the UPS.
4. Close the ferrite bead so that the ferrite bead’s case snaps closed 
with the cable routed through the ferrite bead’s case.
Table 2
DB-9 pin assignment
DB-9
Pin
Assignment Description
1
Low Battery (open collector)
2
UPS TxD (typical RS-232 levels)
3
UPS RxD (typical RS-232 levels)
4
Remote Shutdown (5-12VDC, 10-24mA max; battery operation)
5
Common
6
Remote Shutdown (short to pin 5); all modes of operation
7
Low Battery (open emitter)
8
Utility Fail (open emitter)
9
Utility Fail (open collector)
Pin Assignment
 Collector to Emitter*
* Maximum voltage and current on pins 1, 7, 8 and 9 are 60VDC and 10.0 mA
5
4
3
2
1
6
7
8
9
(-)
(+)
330 Ohms
Open 
Collector
Open 
Emitter
Run cable 
through ferrite 
bead case