Troubleshooting
42
Using the configuration program, the user may specify the number of GXT2-288VBATT external bat-
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 6 shows estimated run times at different loads.
Table 6
Battery run times
Battery/External
Cabinets
Load%
10000VA Run Time
in Minutes
Battery/External
Cabinets
Load%
10000VA Run Time
in Minutes
Internal Battery
10%
107
Internal Battery
+ 1 LRT Battery 
Pack
10%
548
20%
52
20%
284
30%
31
30%
217
40%
22
40%
151
50%
16
50%
107
60%
13
60%
86
70%
10
70%
66
80%
9
80%
55
90%
7
90%
47
100%
6
100%
40
Internal Battery
+ 1 External Battery
Cabinet
10%
251
Internal Battery
+ 2 LRT Battery 
Pack
10%
1030
20%
118
20%
538
30%
74
30%
332
40%
52
40%
269
50%
39
50%
231
60%
32
60%
195
70%
26
70%
158
80%
22
80%
125
90%
19
90%
109
100%
17
100%
96
Internal Battery
+ 2 External Battery
Cabinets
10%
333
Internal Battery
+ 3 LRT Battery 
Pack
10%
1473
20%
216
20%
821
30%
118
30%
520
40%
85
40%
382
50%
66
50%
289
60%
53
60%
264
70%
44
70%
238
80%
38
80%
215
90%
32
90%
189
100%
28
100%
165
Internal Battery
+ 3 External Battery
Cabinets
10%
494
Internal Battery
+ 4 LRT
10%
1973
20%
265
20%
1053
30%
191
30%
672
40%
119
40%
515
50%
92
50%
406
60%
75
60%
304
70%
62
70%
280
80%
54
80%
263
90%
47
90%
243
100%
41
100%
224
Internal Battery
+ 4 External Battery
Cabinets
10%
590
20%
295
30%
236
40%
178
50%
119
60%
98
70%
82
80%
71
90%
61
100%
54