Operating Manual LP 33 Series 30 & 40 kVA 
Automatic bypass operation 
 
In  VFI  (Voltage Frequency Independent) operation 
mode, the load is permanently supplied by the 
inverter but, in case of trouble on the inverter, or 
when overload or short-circuit on the output 
occur, if the mains voltage do not exceed the 
admitted tolerances, the load is instantly 
transferred to the mains through the automatic 
bypass
, taking advantage of the higher short 
circuit power. 
 
Fig. 3.2-3   Energy flow in automatic bypass operation 
 
When the inverter recovers, the load will be re-transferred automatically to the inverter
 
     In case of parallel system 
 
Each unit has its own bypass. 
All the bypasses in the system work together, their control being managed in the same manner by 
all units. 
The units are continuously exchanging information before taking such decision. 
In case the inverter of one unit fails, its bypass remains operating. 
It is excluded only if the unit is separated from the common bus by opening its output switch Q1.
 
 
 
Mains recovery operation 
 
As soon as the mains recovers, the rectifier starts 
up automatically supplying the inverter and the 
battery-charger recharges the battery
 
In case the inverter has been shut down following 
a complete discharge of the battery, when the 
mains recovers the system start up automatically. 
 
Fig. 3.2-4   Energy flow at mains recovery operation 
 
When the energy stored in the battery is sufficient to ensure a minimum time of operation with the 
actual load, in case of a future mains failure, the load will be retransferred to inverter (if selected VFI 
Mode
). 
 
     In case of parallel system 
 
When the AC input power recovers, the rectifiers will start up sequentially according to their 
number in the parallel system in order to avoid an initial inrush current. 
The  inverters will start up automatically, but only when the battery has recharged enough for a 
minimum runtime with the present load. 
When enough inverters to supply the load have been restarted, the load will be transferred from the 
automatic bypass back to the inverter bus-bars