Digital Modules
4-39
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Effect of Errors and Parameter Assignment on the Input Values
The input values of the SM 421; DI 16 
 
 24 DC are affected by certain errors and
the parameter assignment of the module. The following table lists the effects on the
input values.
You will find more diagnostic messages of the module in the Appendix entitled
“Diagnostic Data of the Signal Modules”.
Table 4-15 How the Input Values Are Affected by Faults and by the Parameter Assignment of the 
SM 421; DI 16 
 
 24 VDC 
Diagnostic Message
“Diagnostics”
Parameter
“Reaction to
Error”
Parameter
Input Value of Digital Module
Module not
parameterized
Cannot be
disabled
Not relevant
0 signal (all channels)
No front connector
SV
Parameterized substitute value
KLV
Last read, valid value
Incorrect parameters
(module/channel)
Cannot be
disabled
Not relevant
0 signal (module/all incorrectly
parameterized channels)
STOP operating mode
Cannot be
disabled
Process value (not updated)
Internal voltage failure
Cannot be
di
bl d
SV
Parameterized substitute value
disabled
KLV
Last read, valid value
Hardware interrupt lost
Cannot be
disabled
Not relevant
Current process value
Wire break (for each
h
l)
Deactivated
0 signal
channel)
Activated
SV
Parameterized substitute value
KLV
Last read, valid value
Sensor supply missing
( l
  ti
t d i  
”N
Deactivated
0 signal
(also activated via ”No
Load Voltage L+”)
Activated
SV
Parameterized substitute value
Load Voltage L+ )
KLV
Last read, valid value
No load voltage L+ (for
each channel group)
Deactivated
0 signal, if the contact is connected via the
sensor supply; process value for the
external sensor supply
Activated
SV
Parameterized substitute value
KLV
Last read, valid value