Siemens S7-400 Benutzerhandbuch

Seite von 638
Digital Modules
4-67
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 422; DO 16 
 
 20-125 VDC/1.5 A
Dimensions and Weight
Dimensions W 
 
 H 
 
 D
(in millimeters)
25 
 
 290 
 
 210
Weight
Approx. 800 g
Data for Specific Module
Number of outputs
16
Length of cable
Unshielded
Shielded
Max. 600 m
Max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L1
Reverse polarity protection
20 VDC to 138 VDC
Yes, with fuse
Total current of the outputs 
1)
Up to 40 
C
Up to 60 
C
With fan subassembly
Max. 16 A 21 A
Max. 8 A
14 A
Isolation
Between channels and
backplane bus
Yes
Between the channels
In groups of
Yes
8
Permitted potential difference
Between the outputs of the
different groups
250 VAC
Insulation tested with
1500 VAC
Current consumption
From the backplane bus
From load voltage L +
(without load)
Max. 700 mA
Max. 2 mA
Power dissipation of the
module
Typ. 10 W
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
Diagnostic Interrupt
Parameters can be
assigned
Diagnostic functions
Parameters can be
assigned
Group error display
For internal fault
Red LED (INTF)
For external fault
Red LED (EXTF)
Diagnostic information
readable
Yes
Substitute value can be applied
Yes, programmable
Data for Selecting an Actuator
Output voltage
At signal “1”
 Min. L+ (–1,0 V)
Output current
At signal “1”
Rated value
1.5 A
Permitted range
10 mA to 1.5 A
Permitted surge current
Max. 3 A 
(for 10 ms)
At signal “0” (leakage
current)
Max. 0.5 mA
Output delay (for resistive load)
From “ 0” to “1”
Max. 2 ms
At “1” to “0”
Max. 13 ms
Parallel connection of 2 
outputs
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance
Possible (only outputs
of the same group)
Triggering a digital input
Possible
Switch rate
For resistive load
Max. 10 Hz
For inductive load 
to IEC 947-5-1, DC 13
Max. 0.5 Hz
Short-circuit protection 
of output
Electronically
protected
2)
Threshold on
Typ. 04 A to 5 A
Replacement fuses
Fuse, 8 A/250 V, quick
blow
1) To achieve maximum performance capability, 
distribute the high-current load between the two 
groups.
2) To reset a deactivated output,
 
first set the output signal to 0 and then to 1.
If output signal 1 is written to a deactivated
output and the short circuit remains, additional 
interrupts are generated (provided the diagnostic 
interrupt parameter was set).