Power Supply Modules
3-14
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 3-8
INTF, DC5V, DC24V LEDs, continued
LED
INTF
Remedy
Cause of Fault
DC24V
DC5V
H
D*
D
Short circuit or overload on 5 V and
24 V
Check load on the power supply
module. 
Possibly remove modules
H
D*
H/D **
Short circuit or overload on 5 V
Check load on the power supply
module. Possibly remove modules
H
H
D
If the standby switch is at the
position, illegal external supply on 5 V
Remove all modules. 
Determine which module is faulty
If the standby switch is at the  
I
position, short-circuit or overload on
24 V
Check load on the power supply
module. 
Possibly remove modules
D
B
H
Voltage restored after short circuit or
overload on 5 V if faults occur in
operation
Press FMR momentary-contact
pushbutton: 
Flashing light changes to constant light
Dynamic overload on 5 V
Check load on the power supply
module. 
Possibly remove modules
D
H
B
Voltage restored after short-circuit or
overload on 24 V if faults occur in
operation
Press FMR momentary-contact
pushbutton: 
Flashing light changes to constant light
Dynamic overload on 24 V
Check load on the power supply
module. 
Possibly remove modules
D
B
B
Voltage restored after short circuit or
overload on 5 V and 24 V if faults occur
in operation
Press FMR momentary-contact
pushbutton: 
Flashing light changes to constant light
D
B
B
Dynamic overload on 5 V and 24 V
Check load on the power supply
module. 
Possibly remove modules
D = LED is dark;  L = LED lights up;  F = LED flashing;
* If the power supply module does not start up again after a few seconds once the
overload has been removed, remove power to the module for 5 minutes and then
switch it on again. If the module stills does not start up, you must replace it. This
applies to 6ES7407-0KA01-0AA0, release 3 and for 6ES7407-0KR00-0AA0,
release 
 5.
** Depending on the short-circuit resistance
If either the 5 VDC or 24 VDC LEDs remains dark after switching on, the system
has not powered up.
If either of the 5 VDC or 24 VDC LEDs of the PS 407 10AR remains dark for longer
than 1 or 2 seconds after it is switched on, the power supply module will not start
up.