Troubleshooting 
 
  Make sure that the system has power, and make sure that all voltages are within specification.  
The Neuron chip does not tolerate under- or over-voltage conditions very gracefully. 
 
  Make sure that the driver’s command-line switches (
/P#
 and 
/Q#
) match the jumper settings 
on the module (JP4 and JP5, respectively) 
 
  Sometimes there are conflicts for system resources.  Double-check that the LM104-P50 is set to 
use a base I/O address and interrupt request line that is not used by some other device in the 
system.  Try selecting a different base I/O address, using JP4, and make sure to change the 
driver’s command-line switch (
/P#
) to match.  If this does not resolve the problem, try 
selecting a different IRQ number, using JP5, and make sure to change the driver’s command-
line switch (
/Q#
) to match. 
 
  Occasionally, the Neuron chip’s internal EEPROM memory can become corrupted.  This is 
indicated by the SERVICE LED staying on solid, not blinking at all.  To correct this problem, 
the node must be rebooted, which is not the same as a power up reset or shorting the RESET 
jumper.  There are three different ways of accomplishing this: 
 
1. Run the 
NODEUTIL
 utility (available from Echelon) on the host PC and select Reboot 
(“R”). 
2.  Remove power from the LM104-P50.  Remove the EPROM chip (U2) from its socket 
using a chip extractor.  Replace the EPROM with an EPROM programmed with 
EEBLANK.NRI
 (also available from Echelon).  Turn the power on.  The service LED 
should go off while the Neuron blanks its internal EEPROM.  It will  then come on solid 
and stay that way.  Remove power from the LM104-P50, remove the 
EEBLANK
 
EPROM and replace it with the original EPROM, then restore power. 
3.  Remove power from the  LM104-P50.  Remove the EPROM chip (U2) from its socket 
with a chip extractor, then restore power.  Wait a few seconds, remove power, then 
replace the EPROM in its socket.  This will usually force the Neuron to load the program 
and default configuration into internal EPROM.  Note that this method does not work in 
all cases, but will not harm the board. 
 
If any of these methods do not solve the problem, a Returned Material Authorization (RMA) should 
be obtained from VISTA Electronics and the board returned for service.