The Q7230A provides adjustable range (zero and span) for 
two-wire current or voltage control. Separate potentiometers 
are provided on the circuit module for adjusting the zero point 
and the span. It includes a cw/ccw switch for configuring the 
motor to rotate clockwise or counterclockwise with an 
increase in control signal.
1. Verify that the zero potentiometer is fully clockwise and 
that the span potentiometer is fully counterclockwise.
2. Select desired rotation direction [cw (electrically nor-
mally closed) is the most common]. The following direc-
tions apply for the clockwise setting. For 
counterclockwise setting, reverse open and closed, and 
reverse clockwise and counterclockwise. Remove film 
on switch before use.
3. See Fig. 6 and 7 for typical system wiring.
4. For current control, connect the current input signal to I+ 
(screw terminal 3) and COM (screw terminal 5). For 
voltage control, connect the voltage input signal to V+ 
(screw terminal 1) and COM (screw terminal 5).
5. Set the controller to output the signal required to drive 
the motor to the closed position. Wait for the motor to 
stop driving closed.
6. Turn the zero potentiometer slowly counterclockwise 
 until the motor starts to open.
7. Turn the zero potentiometer slowly clockwise
 
until the motor is fully closed. This is defined as the zero 
setting.
8. Set the controller to output the signal required to drive 
the motor to the fully open position. Wait for the motor to 
stop driving open.
9. Turn the span potentiometer slowly clockwise
 
until the motor starts to drive closed. The difference 
between the fully open position signal and the fully 
closed position signal is defined as the operating span.
10. Recheck the fully closed position and readjust the zero 
potentiometer, if necessary. (Turn the zero potentiome-
ter clockwise
 to close the motor and counter-
clockwise
 to open the motor.)
Fig. 4. Q7230A terminals and adjustments.
Table 2. Q7130A/M91XX Checkout Procedure.
Step
Proper Motor Response Switch in 
Clockwise Position
Switch in Counterclockwise Position
1. Open terminal C or R.
Motor runs closed (fully ccw).
Motor runs open (fully cw).
2. Jumper terminals C and F.
Motor runs fully open (fully cw).
Motor runs fully closed (fully ccw).
3. Remove either T terminal or disconnect 
power supply.
Spring return motors return to normal spring position (fully ccw
 for 
mechanically normally closed motors; fully cw
 for mechanically normally 
open motors).
M27213
T1 T2 F
Com
V+
CCW
CW
ZERO
SPAN
1+