Chapter 4  Display and Operation|ASDA-B Series
 
4-14  
 
Revision January 2009
 
4.1.6  DO Force Output Diagnosis Operation 
For testing, the digital outputs can be forced to be activated (ON) or inactivated (OFF) by using 
parameter P4-06. Follow the setting method in Figure 4.10 to enter into DO force output diagnosis 
operation (OP x) mode (“x” indicates the parameter range from 0 to 7). Pressing UP or DOWN arrow 
key can change “x” value from 0 to 7 (hexadecimal format) and force digital outputs DO1 to DO3 to be 
activated (ON) or inactivated (OFF). The DO function and status is determined by P2-18 to P2-20. This 
function is enabled only when Servo Off (the servo drive is disabled). 
Figure 4.10 
O
F
P
:
0
4 -
6
T
0
SET
P 4 -
0
P 4 -
1
P 4 -
O P
O
F
:
0 6
T
O
F
:
0 6
T
O
F
:
0 6
T
O P
2
O P
Force DO1 to be activated
Force DO2 to be activated
Force DO3 to be activated