Delta Electronics DOP-A/AE/AS Verbindungsanleitung

Seite von 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series 
Revision January, 2008, Doc. Name: 2007PDD23000007 
 
 
1-101 
Modbus nW (Master) --- RTU / ASCII mode 
A. HMI factory settings  
Baud rate:  9600, 7, EVEN, 1. (ASCII) 
 
9600, 8, EVEN, 1. (RTU) 
Controller station number: 1. 
Control area/status area: W40100 / W40200. 
NOTE
 
1)  This driver can read consecutive communication address on the screen via one Modbus command to 
improve the communication efficiency. For example, if there are 6 devices on the screen, and read the 
data of the addresses W40100, W40101, W40102, W40200, W40201, W40300. It will read three times. 
It will read W40100 3 Words at the first time, read W40200 2 Words at the second time and read 
W40300 1 Word at the third time. 
2)  Ensure to check the box next to “Optimize” (Optimization for reading) selection in “Communication” tab in 
the “Configuration” dialog box in “Options” menu (Options Æ Configuration Æ Communication). If 
“Optimize” selection is unchecked, do not select “Data Length Limit”. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data length 
Output Registers 
Wn 
n: 40001 ~ 50000 
N/A 
Word 
Input Registers 
Wn 
n: 30001 ~ 40000 
N/A 
Word 
¾
  Input Registers is “read only”. 
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Discrete Outputs 
Bn 
N/A 
n: 1 ~ 10000 
Discrete Inputs 
Bn 
N/A 
n: 10001 ~ 20000 
¾
  Discrete Inputs is “read only”. 
C. Connections (Connector Pinouts) 
Please refer to 1.1 Pin Definition of Serial Communication for detail.