Delta Electronics DOP-A/AE/AS Verbindungsanleitung

Seite von 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-120  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Siemens S7 200 PLC 
A. HMI factory settings 
Baud rate: 9600, 8, EVEN, 1. 
Controller station number: 2. 
Control area/status area: VW0 / VW10. 
B. Definition of controller Read/Write address 
Register 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Timer 
Tn 
n: 0 ~ 255 
N/A 
Analog Input Word 
AIWn 
n: 0 ~ 30 
N/A 
Counter 
Cn 
n: 0 ~ 255 
N/A 
Analog Output Word 
AQWn 
n: 0 ~ 30 
N/A 
Input Image 
IWn 
n: 0 ~ 14 
N/A 
Input Image 
IDn 
n: 0 ~ 12 
N/A 
Output Image 
QWn 
n: 0 ~ 14 
N/A 
Output Image 
QDn 
n: 0 ~ 12 
N/A 
Special Bits 
SMWn 
n: 0 ~ 199 
N/A 
Special Bits 
SMDn 
n: 0 ~ 197 
N/A 
Internal Bits 
MWn 
n: 0 ~ 98 
N/A 
Internal Bits 
MDn 
n: 0 ~ 96 
N/A 
Data Area 
VWn 
n: 0 ~ 9998 
N/A 
 
(DBWn) 
(n: 0 ~ 9998) 
 
Data Area 
VDn 
n: 0 ~ 9996 
N/A 
Special S 
SWn 
n: 0 ~ 99 
N/A 
Special S 
SDn 
n: 0 ~ 97 
N/A 
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Timer Bit 
Tn 
N/A 
n: 0 ~ 255 
Counter Bit 
Cn 
N/A 
n: 0 ~ 255 
Input Image 
In.b 
n: 0 ~ 15 
b: 0 ~ 7 
Output Image 
Qn.b 
n: 0 ~ 15 
b: 0 ~ 7 
Special Bit 
SMn.b 
n: 0 ~ 200 
b: 0 ~ 7 
Internal Bit 
Mn.b 
n: 0 ~ 99 
b: 0 ~ 7 
Data Area Bit 
Vn.b 
n: 0 ~ 9999 
b: 0 ~ 7