Delta Electronics DOP-A/AE/AS Verbindungsanleitung

Seite von 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-76  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Mitsubishi A Series AJ71UC24 Communication Module 
A. HMI factory settings 
Baud rate: 9600, 8, ODD, 1. 
Controller Station number: 0. 
Control area/status area: D0 / D10. 
NOTE
 
1)  This driver utilizes CheckSum. 
2)  Please set “PLC Mode” switch to position 5. 
3)  If OUTPUT Relay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication and the 
communication will not recover automatically. PLC will need to be manually reset. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data length 
Input 
Xn 
n: 0 ~ 7FF 
N/A 
Word (multiple of 16) 
Output 
Yn 
n: 0 ~ 7FF 
N/A 
Word (multiple of 16) 
Link Relay 
Bn 
n: 0 ~ FFF 
N/A 
Word (multiple of 16) 
Internal Relay 
Mn 
n: 0 ~ 8191 
N/A 
Word (multiple of 16) 
Special Internal Relay 
SMn 
n: 9000 ~ 9255
N/A 
Word (9000 + multiple of 16) 
Latch Relay 
Ln 
n: 0 ~ 2047 
N/A 
Word (multiple of 16) 
Annunciator 
Fn 
n: 0 ~ 2047 
N/A 
Word (multiple of 16) 
Timer Value 
TNn 
n: 0 ~ 999 
N/A 
Word 
Counter Value 
CNn 
n: 0 ~ 999 
N/A 
Word 
Data Register 
Dn 
n: 0 ~ 8191 
N/A 
Word 
Special Data Register 
SDn 
n: 9000 ~ 9255
N/A 
Word 
File Register 
Rn 
n: 0 ~ 8191 
N/A 
Word 
Link Register 
Wn 
n: 0 ~ FFF 
N/A 
Word