Monessen Hearth CSVF30SPV Benutzerhandbuch

Seite von 32
58D56002 
29
OBSERVED PROBLEM
ODS/pilot  lights,  but  flame 
goes out when control knob is 
released.
Burner does not light after ODS/
pilot is lit.
Burner backfires during com-
bustion.
Slight  smoke  or  odor  during 
initial operation.
Logs appear to smoke after ini-
tial operation.
Heater  produces  a  whistling 
noise when burner is lit.
No gas to pilot. 
POSSIBLE CAUSE
1.  Control knob not fully pressed in.
2.  Control knob not pressed in long enough.
3.  Appliance shutoff valve not fully open.
4.  Thermocouple  connection  loose  at  control 
valve.
5.  Pilot flame not touching thermocouple, which 
allows  thermocouple  to  cool,  causing  pilot 
flame to go out. 
6.  Thermocouple damaged.
7.  Control valve damaged.
1.  Inlet gas pressure is too low.
2.  Burner orifice diameter is too small.
3.  Burner orifice is clogged.
1.  Manifold pressure is too low.
2.  Burner orifice is clogged.
1.  Burner orifice is clogged or damaged.
2.  Burner is damaged.
3.  Gas regulator defective.
1.  Vapors from paint or curing process of logs.
1.  Turning control knob to HIGH position when 
burner is cold.
2.  Air in gas line.
3.  Dirty or partially clogged burner orifices.
1.  LP-regulator shut down due to inlet pressure 
too high.
REMEDY
1.  Press in control knob fully.
2.  After  ODS/pilot  lights,  keep  control 
knob pressed in for 30 seconds.
3.  Fully open manual shutoff valve.
4.  Hand tighten thermocouple connection 
until snug, then tighten 1/4 turn more.
5.  Contact local gas company. This prob-
lem could be caused by either low gas 
pressure, or a dirty or partially clogged 
ODS/pilot.
6.  Replace pilot.
7.  Replace control valve.
1.  Contact qualified service person.
2.  Replace burner orifice.
3.   Clean orifice.
1.  Contact local gas company.
2.  Clean burner or replace burner orifice.
1.   Clean burner or replace burner orifice.
2.  Replace burner.
3.  Replace gas regulator.
1.  Problem will stop after a few hours of 
operation. Open a window for the first 
few hours.
2.  Log heater is intended to be smokeless. 
Turn OFF heater and call qualified ser-
vice person.
1.  Turn control knob to LOW position and 
let warm up for a minute.
2.  Operate burner until air is removed from 
line. Have gas line checked by local gas 
company.
3.   Clean burner or replace burner orifice.
1.  Verify LP tank regulator is installed and 
set at 11" to 13" w.c.
TROUBLESHOOTING
If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and 
the heater may backfire when lit. If the gas quality or pressure is low, contact your local 
gas supplier immediately. 