 L676-1 Direct Vent Gas Fireplace
20
INST
ALLA
TION
Horizontal Venting with Two (2) 90
o
 Elbows
Horizontal Venting with Three (3) 90
o
 Elbows
One 90
o
 elbow = Two 45
o
 elbows.
 Option      V 
         H + H1
     A) 
2'  Min.       4' Max.
     B) 
3'  Min.       6' Max.
     C) 
4'  Min.       8' Max.
     D) 
5'  Min.            9'  Max. 
     E) 
6' Min.       10' Max.
W i t h   t h e s e   o p t i o n s , 
maximum total pipe length 
is 30 feet with minimum 
of 6 feet total vertical and 
maximum 10 feet total 
horizontal.
Please note minimum 1 foot between 90
o
 elbows is 
required.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.
INSTALLATION
One 90
o
 elbow = Two 45
o
 elbows.
Option      V 
  H          V + V1   H + H1
     A) 
2' Min.  1' Max.  3' Min.    2' Max.
     B) 
2' Min.  2' Max.  5' Min.   4' Max.
     C) 
3' Min.  2' Max.  7' Min.    5' Max.
     D) 
4' Min.  3 Max.  9' Min.   6' Max.
     E) 
5' Min.  4' Max.  10' Min.   7' Max.
     F) 
6' Min.  6' Max.  11' Min.   9' Max.
With these options, max. 
total pipe length is 30 feet 
with min. of 11 feet total 
vertical and max. 9 feet total 
horizontal.
Please note min. 1 foot 
between 90
elbows is 
required.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.