STRYKER VAV USER GUIDE
23
62-2030—01
Two point calibration
You can start either maximum or minimum balancing in any 
order. The tool does not enforce any rules on the order of 
balancing.
Maximum calibration
To start maximum calibration:
Click 
Start Maximum Balancing.
The device adjusts the damper to try and attain the maximum 
flow setpoint. After the setpoint is attained, the Measured Flow 
field is enabled and the actual measured flow value can be 
entered. The device remains in manual mode (Open 
Maximum) after maximum balancing is complete.
Minimum calibration
To start minimum calibration:
Click 
Start Minimum Balancing.
The device adjusts the damper to try and attain the minimum 
flow setpoint. After the set point is attained, the Measured 
Flow field is enabled and you can enter the actual measured 
flow value. The device remains in manual mode (Open 
Minimum) after minimum balancing is complete.
K Factor calibration
To start K factor calibration method:
Click 
Start K Factor Balancing.
After a warning message, the two point calibration data is 
returned to factory defaults.
The device adjusts the damper to try and attain the maximum 
flow setpoint. After the setpoint is attained, the Measured Flow 
field is enabled and the actual measured flow value can be 
entered.
After the measured flow is entered, the K factor value is 
calculated by the tool and displayed. The tool prompts you to 
write this value to the device. You can choose to calculate the 
K factor without using the tool and set the calculated value in 
the K factor field. The device remains in manual mode (Open 
Maximum) after K factor balancing has been completed.
Heating coil water flow calibration
To override the reheat valve position:
Type the reheat value in percentage and click the Override 
button next to Reheat Valve Override field.
To override the peripheral heat valve position:
Type the peripheral heat value in percentage and click the 
Override button next to the Peripheral Heat Valve Override 
field.
NOTE: Note: Click the Auto button to set the reheat and 
peripheral heat valve into automatic operation.
Setting the device mode to automatic operation
To set the device to automatic operation:
Click 
Set Mode to Auto when it is enabled.
While exiting the view if the device is in manual mode, the tool 
prompts you to change the mode to automatic operation.
Restoring to factory defaults
To restore to factory defaults:
Click the 
Restore to Factory Defaults button to restore the 
default value of the Zero calibration values, K factor calibration 
values, Minimum flow calibration values and Maximum flow 
calibration values.
RELATED TOPICS
15. MONITORING
Use this page to monitor the critical parameters for an Stryker VAV device on the LON network. This action can be performed with 
the device in online mode. The controller must be in a commissioned state.
To monitor:
Step
Action
1
From the 
Nav menu, choose Station > Driver > LON network > AscLonVAV device.
2
Right-click the device and choose 
Views > Monitor from device items. The Monitor screen appears.
3
If required, you can enter the values in the editable fields.
4
Click 
Write to write edited values to the controller.