Emerson 3412 User Manual

Page of 144
Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual
Section 4: Configuration
3-9000-759 Rev D
June 2014
Using AMS Device Manager to configure the meter
 87
AMS Device Manager - Manual Setup
Use the 
Manual Setup
 wizard to configure the meter’s parameters. 
 an
 
and from the AMS Device Manager Configure menu click
 Manual Setup
Figure 4-8  AMS Device Manager - Configure Manual Setup
Procedure
1.
If installed, remove security wires from the endcap and the Bracket/Cover hex head 
bolts that secures the Base Enclosure.
1.
Disable the Write Protect switch in the CPU Module to write any of the following 
configuration parameters to your meter.
2.
Click the 
Device Variables Mapping
 tab. The Primary and Secondary variables are read 
only and are configured for Uncorrected Flow Rate. The Third and Fourth variable 
configuration choices include Pressure and Temperature. 
3.
Click the
 Units
 tab 
(see
 
).
4.
Click the 
Analog Output 1 (HART)
 tab (see 
).
5.
Click the 
Analog Output 2
 tab. Follow the configuration instructions in the 
. The read only Secondary variable Content, 
Uncorrected Flow Rate, displays. Use the drop-down arrow and select the (flow) 
Direction - Forward or Reverse. Enter a Lower and Upper Range limit. Set the Alarm 
Action parameters. Click 
Apply
, after you enter the data to write the parameters to the 
meter.