Quick Start Wizard
The Quick Start wizard groups together all the settings you need to make for a simple 
application. 
The wizard is a complete package and settings are inter-related. 
Do not use the wizard to modify individual parameters.
You can access the Quick Start wizard either via SIMATIC PDM, or via the handheld 
programmer.
There is no need to perform a reset before a Quick Start.
1. Quick Start 
In SIMATIC PDM, Open the menu Device – Quick Start, and follow steps 1 to 5.
If you are using the handheld programmer, activate program mode and work 
through the Quick Start sequence.
1.1. Language 
1.2. Application Type 
1.3. Operation 
Operation types
Options
ENGLISH, DEUTSCH, FRANCAIS, ESPANOL
Options
STEEL
Silo construction
CONCRETE
Options
LEVEL
Distance to material surface referenced from Low 
Calibration Point (process empty level).
SPACE
Distance to High Calibration Point (process full level) 
referenced from material surface.
DISTANCE
Distance to material surface referenced from Sensor 
Reference Point.
SITRAN
S LR 40
0
high 
calibration 
point
low calibration point
level
space
distance
sensor reference point 
(flange face)