Configuration
To configure a PROFIBUS PA Class 1 Master (for example, a PLC), you will need a
GSD file.
GSD file.
The GSD file
The GSD file SIEM8132.gsd is available from the SITRANS LR 460 product page on our
web site. Go to https://pia.khe.siemens.com/index.asp?Nr=14655 and click Downloads.
Download the DeviceInstall, and run it from your computer. This will install the GSD file
into your system (as long as you are using SIMATIC software).
web site. Go to https://pia.khe.siemens.com/index.asp?Nr=14655 and click Downloads.
Download the DeviceInstall, and run it from your computer. This will install the GSD file
into your system (as long as you are using SIMATIC software).
Setting the PROFIBUS address
When your instrument is shipped, the PROFIBUS address is set to 126. You can set it
locally (see below) or remotely via the bus, using a parameterization tool such as
SIMATIC PDM (see
locally (see below) or remotely via the bus, using a parameterization tool such as
SIMATIC PDM (see
• Point the handheld programmer at the display then press Mode
to
activate
PROGRAM mode, menu item 1.0.
• Press Down ARROW
, Right ARROW ,
Right ARROW
to navigate to
Address (menu item 2.1.2).
• Press Right ARROW
to open Edit mode: the PROGRAM icon will flash.
• If required, key in a new value and press Right ARROW
to accept it. The LCD
displays the new value and the PROGRAM icon disappears.
Configuring a new device: procedure
1.
You will need the most up-to-date Device Description (DD) for your instrument.
Launch SIMATIC PDM – Manager Device Catalog, browse to the unzipped DD file
and select it.
and select it.
2.
Launch SIMATIC Manager and create a new project for LR 460. Application Guides
for setting up HART and PROFIBUS PA devices with SIMATIC PDM.can be
downloaded from the product page of our website at:
https://pia.khe.siemens.com/index.asp?Nr=14655
downloaded from the product page of our website at:
https://pia.khe.siemens.com/index.asp?Nr=14655
3.
Open the Menu Device – Reset and click on Factory Reset.
4.
Upload parameters to the PC/PG.
5.
Calibrate the device. See
Note:
If you are not using SIMATIC software, you can download the GSD file
separately, and import it with the software you are using.
Values
Range: 0 to 126 (We recommend a setting in the range 1 to 125.)
Pre-set: 126
Pre-set: 126