CSB GP12400 Leaflet

Page of 2
Cells Per Unit
6
Voltage Per Unit
12
Capacity
40A h @ 20hr-rate to 1.75V per cell @25
(77 )
Weight
Approx. 12.63 kg(27.84 lbs)
Maximum Discharge Current
400A(5sec)
Internal Resistance
Approx. 8.1m
Operating Temperature Range
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
Recommended Maximum Charging
12A
Current Limit
Equalization and Cycle Service
Self Discharge
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
B2-L terminal to accept M5 nut & bolt
Container Material
ABS(UL 94-HB/File E50263)*Flammability resistance of
(UL 94-V0/File E88637) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 (  5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
GP 12400
12V  40Ah
Specification
Powered by
GP 12400   is a general purpose battery up to 5 years in standby 
service or more than 260 cycles at 100% discharge in cycle 
service. As with all CSB batteries, all are rechargeable, highly 
efficient, leak proof and maintenance free.
RA: 08
Width (W)
Dimensions : 
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
170±2 (6.69±0.08)
168.5±2 (6.63±0.08)
197±2 (7.76±0.08)
165±2 (6.5±0.08)
F.V/Time
5MIN
10MIN
15MIN
30MIN
1HR
2HR
3HR
4HR
5HR
8HR
10HR
20HR
1.60V
176
113
85.0
51.8
30.6
17.7
12.6
9.83
8.01
5.25
4.28
2.21
1.67V
157
105
81.0
50.8
30.3
17.6
12.5
9.77
7.98
5.19
4.20
2.12
1.70V
149
101
78.7
50.1
30.2
17.5
12.4
9.75
7.96
5.17
4.16
2.08
1.75V
135
95.0
75.5
49.0
30.0
17.4
12.3
9.71
7.93
5.10
4.09
2.01
1.80V
121
88.3
71.7
47.6
29.8
17.3
12.2
9.67
7.89
5.03
4.03
1.93
1.85V
107
81.7
67.8
46.2
29.4
17.2
12.1
9.63
7.85
4.96
3.96
1.86
F.V/Time
5MIN
10MIN
15MIN
30MIN
1HR
2HR
3HR
4HR
5HR
8HR
10HR
20HR
1.60V
2,110
1,350
1,020
622
367
212
151
118
96.1
63.0
51.3
26.5
1.67V
1,886
1,259
972
606
364
211
150
117
95.7
62.3
50.4
25.4
1.70V
1,790
1,214
945
600
363
210
149
116
95.5
62.0
50.0
24.9
1.75V
1,620
1,140
902
585
360
209
148
115
95.2
61.2
49.2
24.1
1.80V
1,450
1,060
860
571
357
208
147
114
94.8
60.4
48.3
23.2
1.85V
1,280
980
814
555
353
207
146
113
94.2
59.6
47.5
22.4
13.5 to 13.8 VDC/unit Average at  25 (77 )
14.4 to 15.0 VDC/unit Average at  25 (77 )
CSB-manufactured
VRLA 
batteries are UL-
recognized components
under UL924 and UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com) 
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified