7.  A readily accessible disconnect device shall be incorporated in the building installation 
wiring. 
8.  A suitable listed circuit breaker shall be provided in the building installation as the unit’s 
disconnect device.  The branch circuit rating (i.e. minimum 15A listed circuit breaker, 
etc.). 
DC Power Wiring, Replacing Power Supply and Fans 
DC Power Supply Wiring Instructions 
The following image shows the wiring configuration for a 48 VDC power supply in a negative 
ground system application.  For positive ground system applications remove the chassis 
ground shorting jumper and connect it between the positive terminal and the chassis ground 
terminal.  Alternatively, the chassis grounding jumper can be eliminated and the chassis 
ground connected at the power source.  The ground terminal and the negative terminal are 
not connected inside the iMediaChassis/3. 
 
DC Power Supply 
Negative ground system configuration (default position) 
 
 
NOTE 
Incorrect wiring will result in chassis malfunction. 
 
The 3-Slot Desktop Chassis is compliant with Isolated Grounding Plane practices.  The 
POSITIVE and NEGATIVE terminals are isolated from chassis ground and must have a ground 
reference at the power-sourcing equipment. 
Power Supply Modules 
Power supply in all models of the 3-Slot Desktop Chassis are fixed, and not end-user 
replaceable.