Air supply (make-up air) must be given careful consideration to ensure proper performance of each dryer.  An
unrestricted source of air is necessary for each dryer.  An airflow of 2,100 cfm (cubic feet per minute) (59.5 cmm
[cubic meters per minute]) must be supplied to each dryer.  As a general rule, an unrestricted air entrance from
the outdoors (atmosphere) of a minimum of 3 square feet (0.28 square meters) is required for each dryer.
To compensate for the use of registers or louvers used over the openings, this make-up air area must be
increased by approximately thirty-three percent (33%).  Make-up air openings should not be located in an area
directly near where exhaust vents exit the building.
It is not necessary to have a separate make-up air opening for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner that the make-up air is distributed equally to ALL
the dryers.  The dryer must be installed with provisions for adequate combustion and make-up air supply.
EXAMPLE: For a bank of six (6) gas dryers, two (2) openings measuring 3 feet by 3 feet (0.91 meters by 0.91
meters) are acceptable.
Allowances must be made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low pressure areas.
IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes.
Make-up air that is contaminated by dry cleaning solvent fumes will result in
irreparable damage to the motors and other dryer components.
NOTE: Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.
E.  EXHAUST REQUIREMENTS
1. General Exhaust Ductwork Information
Exhaust ductwork should be designed and installed by a qualified professional.  Improperly sized ductwork
will create excessive back pressure, which results in slow drying, increased use of energy, overheating of
the dryer, and shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler)
hi-heat thermostats.  The dryer must be installed with a proper exhaust duct connection to the outside.
CAUTION: This dryer produces combustible lint and must be exhausted to the outdoors.